Inspection
Inspection Details
Equipment ID
10638
10638
Inspection Date
2/8/2024
2/8/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
00
00
External ID
e4877236-2523-46c6-979f-eda712022dc0
e4877236-2523-46c6-979f-eda712022dc0
Location
Ford Truck Paint Facility
1601 Claycomo Rd, Claycomo, MO
Phone: (816) 459-1820
1601 Claycomo Rd, Claycomo, MO
Phone: (816) 459-1820
Owner
Attn: Ford Truck Paint Facility
Ford Truck Paint Facility
PO Box 11009, Kansas City, MO 64119
Phone: (000) 000-0000
Ford Truck Paint Facility
PO Box 11009, Kansas City, MO 64119
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | A portion of the carlights not working | 12/30/2019 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)10 | Missing lock cover on access box allowing for non authorized entry. | 12/30/2019 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | remove standing water and oil in pit | 12/30/2019 | ||
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)3 | Water contaminated the system, contaminated oil removed from tank and replaced but jack and lines recontaminate oil needs repalced | 12/30/2019 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Remove water/oil and debris from pit | 12/17/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Remove oil/water standing in pit | 12/17/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Remove debris from pit | 10/28/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | DOOR INTERLOCK ALLOWING DOOR TO OPEN IN MOTION (UNIT LOCKED OFF AT THIS TIME BY MECHANIC) | 2/9/2024 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | REMOVE OIL/DEBRIS FROM PIT | 2/9/2024 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | PHONE NOT WORKING/DOES HAVE WORKING ALARM BELL | 2/9/2024 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | x | EMERGENCY PHONE NOT RINGING TO SECURITY | 10/25/2024 | |
| A17.1-2016 : Elevators | 1.1 - Door Reopening Device | 8.11.2.1.1(a) | SAFETY EDGE ON INNER DOOR NOT WORKING | 10/25/2024 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | REMOVE STANDING OIL/WATER FROM PIT | 10/25/2024 |