Inspection
Inspection Details
Equipment ID
6079
6079
Inspection Date
2/6/2024
2/6/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
26
26
External ID
713af374-9009-4928-9f8d-a4979bc7db45
713af374-9009-4928-9f8d-a4979bc7db45
Location
Arch Hotel Project Owner LLC
315 Chestnut St, St. Louis, MO
Phone: (314) 655-1234
315 Chestnut St, St. Louis, MO
Phone: (314) 655-1234
Owner
Attn: Hank Hermes, Director of Engineering
Hyatt Regency St Louis at the Arch
N 4th St at Chestnut St, St. Louis, MO 63102
Phone: (314) 294-4660
Alt Phone: (314) 393-2435
Email: hank.hermes@hyatt.com
Hyatt Regency St Louis at the Arch
N 4th St at Chestnut St, St. Louis, MO 63102
Phone: (314) 294-4660
Alt Phone: (314) 393-2435
Email: hank.hermes@hyatt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Replace suspension ropes - Reduced diameter and rouging | 5/1/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.3.3.3 Runby & Clearances After Reroping or shortening | x | Counterweight runby is 0". Shorten hoistway cable to maintain 6" of runby. | 5/27/2020 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean pit | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | clean cartop | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace worn guide shoes on counterweight | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace missing hoistway door gibs on 9th and 2nd floor | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Hoist ropes shall be shortened so that the car can make the final limit without compressing the buffer more than 25%. Re-inspection of ropes and retesting buffers and buffer switches required within 14 days | 4/30/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Need to replace the cover on the door operator. | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency generator testing needs to be performed. Re-inspection required | 4/30/2025 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Need to clean pit | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Need to clean car top | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Need to replace missing hoistway door gibbs on 9th & 2nd floor doors | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Re-inspection violation reported 2/6/24 has not been checked yet. Hoist ropes shall be shortened so that the car can make the final limit without compressing the buffer more than 25%. Re-inspection of ropes and retesting buffers and buffer switches required. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Emergency power operation shall be tested. | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | To finish the 5 year full load test the following items must be tested: full load slide test, gov pull-out/pull thru, electrical trip speed, mechanical trip speed, and crush car buffer with full load shall. |