Inspection
Inspection Details
Equipment ID
6071
6071
Inspection Date
2/7/2024
2/7/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
74c768c7-101a-4475-a54c-41501e4f928c
74c768c7-101a-4475-a54c-41501e4f928c
Location
Arch Hotel Project Owner LLC
315 Chestnut St, St. Louis, MO
Phone: (314) 655-1234
315 Chestnut St, St. Louis, MO
Phone: (314) 655-1234
Owner
Attn: Hank Hermes, Director of Engineering
Hyatt Regency St Louis at the Arch
N 4th St at Chestnut St, St. Louis, MO 63102
Phone: (314) 294-4660
Alt Phone: (314) 393-2435
Email: hank.hermes@hyatt.com
Hyatt Regency St Louis at the Arch
N 4th St at Chestnut St, St. Louis, MO 63102
Phone: (314) 294-4660
Alt Phone: (314) 393-2435
Email: hank.hermes@hyatt.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Repair gate reopening devices and light rays on front and rear freight doors | 5/1/2019 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Clean oil from elevator machine room. | 2/3/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.30 - Hydraulic Power Unit | 8.11.3.1.2(m) | Hydraulic tank is leaking fluid. | 2/3/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.14 - Hoistway clearances | 8.11.2.1.3(t) | Rear hoistway facia is rubbing car gate and cab while car is in flight. Repair facia. | 2/3/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | Repair hoistway access pull box on main landing - it will not lock. | 2/3/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | Hold position on Phase 2 fire service does not work properly. Thirty (30) days to repair and reinspect. Did not red tag. | 2/11/2021 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Written maintenance control program shall be provided on-site for each elevator. | 12/19/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | OSV not sealed. Perform test on valve on or before next annual inspection. | 12/19/2022 | ||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency alarm does not work on normal or battery power. | 2/7/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in machine room is expired. replace or have serviced | |||
MO Minimum : Elevators | (I) - Pits | (I)1 | pit needs to be cleaned | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Maintenance control program needs to be updated | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Kellem grip on front car gate reversing edge cable is broken. Replace same | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 2.14.7 | Cartop light bulb on rear needs replacing. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.12 | Hoistway doors have excessive gap when closed (no more than 3/4") at all floors, especially @ 2. Adjust same. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency alarm does not work on normal or battery power. Re-inspection required | 2/7/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in machine room is expired, replace or have serviced | |||
MO Minimum : Elevators | (I) - Pits | (I)1 | Pit needs to be cleaned | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Kellum grip on front car gate reversing edge cable is broken, needs to be replaced | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 2.14.7 | Cartop light bulb on rear needs replacing | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency alarm does not work on normal or battery power. Re-inspection required | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | Pit needs to be cleaned | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Kellum grip on front car gate reversing edge cable is broken, replace same | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 2.14.7 | Cartop light bulb on rear needs replacing |