Inspection
Inspection Details
Equipment ID
14861
14861
Inspection Date
10/3/2018
10/3/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Dustin Schmidt
Dustin Schmidt
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
8dbd3409-9d43-46d4-aa1f-a2321d5bf3d2
8dbd3409-9d43-46d4-aa1f-a2321d5bf3d2
Location
Westchase Building
10845 OLIVE BLVD, CREVE COEUR, MO
10845 OLIVE BLVD, CREVE COEUR, MO
Owner
Scott Properties
1065 EXECUTIVE PARKWAY DR STE 300, CREVE COEUR, MO 63141-6368
1065 EXECUTIVE PARKWAY DR STE 300, CREVE COEUR, MO 63141-6368
Billing
Attn: Tina Moser, Property Manager
1065 EXECUTIVE PARKWAY DR STE 300, SAINT LOUIS, MO 63141-6368
1065 EXECUTIVE PARKWAY DR STE 300, SAINT LOUIS, MO 63141-6368
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | No audible or visual signal on phase 1 fire service. | 8/2/2018 |
| conversion | conversion | n/a | No | No | Replace expired battery in door restrictor control box. | 9/23/2019 |
| conversion | conversion | n/a | No | No | In car emergency light shall work. | 9/23/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | In cab emergency lights shall work. | 9/23/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In cab emergency alarm bell shall work. | 10/3/2018 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Door re-opening device (eye ray), sensitive to smoke, shall be overridden during Phase 1 and Phase 2 fire service operation. | 10/3/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Existing pit light shall work. | 9/23/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | Existing car door restrictor shall work. - Reinspection Required | 9/23/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The emergency lights and bell shall work. | 9/23/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | The carpet inside the elevator car is worn and frayed, creating a possible tripping hazard. Repair or replace as needed. | 9/23/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 9/23/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 7/27/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | There were no fire service keys to test fire service. Keys shall be kept on-site and fire service shall be tested. | 11/28/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | The Phase 1 fire service indicator light is not working. | 7/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Car emergency light shall be operational. |