Inspection
Inspection Details
Equipment ID
10867
10867
Inspection Date
2/14/2024
2/14/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
NA
NA
External ID
1d33d2d5-e513-4cc7-ad8b-db0888d0463b
1d33d2d5-e513-4cc7-ad8b-db0888d0463b
Location
St. Louis Place
200 N Broadway, St. Louis, MO
Phone: (314) 241-0082
200 N Broadway, St. Louis, MO
Phone: (314) 241-0082
Owner
Attn: Cushman & Wakefield
BPRE St. Louis Holdings, LLP
200 N Broadway, Ste 820, St. Louis, MO 63102
Phone: (314) 241-0082
Email: tiara.nash@cushwake.com
BPRE St. Louis Holdings, LLP
200 N Broadway, Ste 820, St. Louis, MO 63102
Phone: (314) 241-0082
Email: tiara.nash@cushwake.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | REpair phone in car | 1/9/2020 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state certificate in machine room | 3/22/2024 | ||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service test & document on log | 3/22/2024 | ||
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Replacehoist ropes--red rouge & reduced diameter within 30 days | 1/26/2022 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Replace missing duct cover on top of the car | 3/22/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace missing section of the duct cover on the top of the car | 3/22/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Repair/replace greenfield to fan top of the car | 3/22/2024 | ||
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Replace hoist ropes red rouge reduced diameter within 30 days | 2/8/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Repair emergency light in the car | 2/8/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Repair the phone in the car | 2/8/2023 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state certificate in machine room | 2/5/2024 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state certificate in machine room | 1/20/2024 | ||
A17.1-2016 : Elevators | 3.20 - Governor rope | 8.6.3.4 | x | Governor ropes has multiple strands broken needs replacement 30 maximum on respection | 2/14/2024 | |
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Phase II fire service operation not working 14 day maximum on reinspection | 2/14/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2 Replacement of Suspension Means (Re-Inspection) | x | Inspection for replacement of governor rope has not been completed yet. State has granted an extension | 6/3/2024 |