Inspection
Inspection Details
Equipment ID
7852
7852
Inspection Date
2/14/2024
2/14/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
425
425
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
322ed271-5d73-4fff-b2d8-54237694a332
322ed271-5d73-4fff-b2d8-54237694a332
Location
Sigma Chemical-Dekalb Bldg
3500 Dekalb St, St. Louis, MO
Phone: (314) 713-4729
Email: chuck.montgomery@milliporesigma.com
3500 Dekalb St, St. Louis, MO
Phone: (314) 713-4729
Email: chuck.montgomery@milliporesigma.com
Owner
Attn: John Klipsch
Sigma Chemical
PO Box 14508, St. Louis, MO 63178
Phone: (314) 771-5765 Ext: 3968
Email: john.klipsch@milliporesigma.com
Sigma Chemical
PO Box 14508, St. Louis, MO 63178
Phone: (314) 771-5765 Ext: 3968
Email: john.klipsch@milliporesigma.com
Billing
Attn: John Klipsch
Sigma Chemical
3300 S 2nd St, St. Louis, MO 63118
Phone: (314) 771-5765 Ext: 3968
Email: john.klipsch@milliporesigma.com
Sigma Chemical
3300 S 2nd St, St. Louis, MO 63118
Phone: (314) 771-5765 Ext: 3968
Email: john.klipsch@milliporesigma.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Clean pit | 7/5/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean pit | 7/5/2023 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.6 | No | No | Front and rear gate off track. Repair | 7/5/2023 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Hoistway door safety access toggle switches inopertive on all floors. | 7/5/2023 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light and alarm inoperative on battery back-up. | 6/9/2020 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Hoistway door safety access toggle switches inoperative on all floors. | 7/5/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in elevator machine room | 5/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 5/22/2023 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Hoistway door safety access toggle switches shall be operable at all landings | 5/22/2023 |
| A17.1-1996 : Elevators | 1.1 - Door Re-opening device | 1001.2(a)(1) | No | No | Repair inoperable gate reversing edge on front car gate. Re-inspection required | 5/22/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 7/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing hoistway/car door/gate pull straps as needed. | 7/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing cotter pin on car door rods (2). | 7/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing hoistway doorlock interlock cover at 2nd floor. | 7/5/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights were flickering during testing, repair as needed. | 7/5/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 9/24/2024 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | No | No | Light on cartop shall work, needs repaired | 9/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Hoistway door safety access toggle switches shall be operable at all landings | 9/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Need to repair inoperable gate reversing edge on front car gate. Re-inspection required | 9/3/2024 |