Inspection
Inspection Details
Equipment ID
1433
1433
Inspection Date
10/22/2018
10/22/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Mark Brown
Mark Brown
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
a2545979-3ae0-4a35-ab2c-8d8f7dae9e8f
a2545979-3ae0-4a35-ab2c-8d8f7dae9e8f
Location
Macy's- South County
10 S COUNTY CENTER WAY, SAINT LOUIS, MO
10 S COUNTY CENTER WAY, SAINT LOUIS, MO
Owner
Macy's
7 W 7TH ST 19TH FL, CINCINNATI, OH 45202-2424
7 W 7TH ST 19TH FL, CINCINNATI, OH 45202-2424
Billing
Attn: Macy's
7 W 7TH ST 19TH FL, CINCINNATI, OH 45202-2424
7 W 7TH ST 19TH FL, CINCINNATI, OH 45202-2424
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | Yes | Brake test failed.. RED TAGGED out of service | 11/8/2018 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(B) | No | No | step has broken tread, needs replacing | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(B) | No | No | Need code compliant caution signage at bottom | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | No | Two com plates missing tooth needs replacing | |
| A17.1-2016 : Elevators | 8.12 - Steps, step chains, and trusses | 8.6.8.13 | No | No | Full clean down of truss needed | |
| A17.1-2016 : Elevators | 7.9 - Steps and upthrust device | 8.6.8.6 | No | No | Step thread broken needs replacing | |
| A17.1-2016 : Elevators | 7.19 - Maintenance records | 8.6.1.2.1(b) | No | No | Need maintenance control plan and place on controller | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.7 Rollers, Tracks, and Chains | Yes | No | Repair step chains. Unit red tagged | 11/19/2021 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current state certificate in machine room | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current state certificate in machine room | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Replace broken (chipped) treads | 10/19/2023 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current state certificate in machine room | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.3 Step/Skirt Performance Index | Yes | No | Step indexing failed reinspection item 30 day maximum | 2/6/2025 |
| A17.1-2016 : Elevators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.6.8.15.1 | No | No | Clean machine pits at upper and lower ends. | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post certificate in machine room. |