Inspection
Inspection Details
Equipment ID
26504
26504
Inspection Date
2/14/2024
2/14/2024
Inspection Type
New Installation
New Installation
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
NA
NA
Slide
8 3/8"
8 3/8"
Governor Rope Pull
50/112
50/112
Door Closing Force
14F/16R
14F/16R
External ID
d191a4af-147e-4617-8395-924f5cfef72f
d191a4af-147e-4617-8395-924f5cfef72f
Location
8400 Delmar
8400 Delmar Blvd, University City, MO
Phone: (000) 000-0000
8400 Delmar Blvd, University City, MO
Phone: (000) 000-0000
Owner
Attn: McKenzie-Anna Purna One LLC
McKenzie-Anna Purna One LLC
1 N Taylor Ave, St. Louis, MO 63108
Phone: (000) 000-0000
McKenzie-Anna Purna One LLC
1 N Taylor Ave, St. Louis, MO 63108
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car. | 5/8/2024 |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | Yes | No | 2.11.11.1(b) - Landing sills to be substantially flush with the floor surface of the elevator landings. | 5/8/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | Top of hoistway:(2) 4 x 4 boxes are missing KO plugs. | 5/8/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | Pit: (1) 4 x 4 box is missing KO plugs. | 5/8/2024 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Yes | No | Pit: Lighting conduit needs to be secured. | 5/8/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | Yes | No | Pit sump pump cover is required. | 5/8/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | Yes | No | 2.2.4.2.4 - A clear distance of not less than 115 mm from the centerline of the rungs, cleats, or steps to the nearest permanent object in back of the ladder shall be provided. | 5/8/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Operating Certificate shall be posted in machine room. | 4/16/2025 |
| A17.1-2016 : Elevators | 3.14 - Hoistway clearances | 2.5 | No | No | Front door clutch shall have proper clearance to hoistway sill. Clutch is striking the hoistway sill on multiple floors. | 4/16/2025 |
| A17.1-2016 : Elevators | 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators | 2.27.1 | Yes | No | Phase 1 operating instruction shall be posted in hall. | 7/7/2025 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Emergency Light shall be operation and lens replaced (led board is bad) | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel | Yes | No | Phase II, Rear door open and door close shall operate only with continuous pressure. | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Machine roomless battery rescue operation (Schindler PEBO) shall be made operational. |