Inspection
Inspection Details
Equipment ID
10635
10635
Inspection Date
2/19/2024
2/19/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Michael Wallis
Michael Wallis
Relief Valve Pressure
435
435
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
24
24
External ID
cb393f7a-5cff-487c-9fab-85c9223b19ab
cb393f7a-5cff-487c-9fab-85c9223b19ab
Location
Holiday Inn- Forest Park
5915 Wilson Ave, St. Louis, MO
Phone: (314) 645-0700
5915 Wilson Ave, St. Louis, MO
Phone: (314) 645-0700
Owner
Attn: LHM
LHM
5915 Wilson Ave, St. Louis, MO 63110
Phone: (000) 000-0000
LHM
5915 Wilson Ave, St. Louis, MO 63110
Phone: (000) 000-0000
Billing
Attn: Ben Jacob
Holiday Inn- Forest Park
5915 Wilson Ave, St. Louis, MO 63110
Phone: (314) 450-2173
Alt Phone: (314) 645-0700
Fax: (314) 450-2170
Email: bjacob@hiforestparkmo.com
Holiday Inn- Forest Park
5915 Wilson Ave, St. Louis, MO 63110
Phone: (314) 450-2173
Alt Phone: (314) 645-0700
Fax: (314) 450-2170
Email: bjacob@hiforestparkmo.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Life jacket/plunger gripper would not stop car in the down direction. Unit Red-Tagged. | 1/9/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Unit has a Phase 1 fire service key switch located at the 1st and 2nd floor. The 2nd floor switch does not appear to function. Identify function of the switch or eliminate. | 1/9/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Provide Phase 1 fire service operating instructions on the 1st floor. | 1/9/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Unit has a Phase 1 fire service key switch located at the 1st and 2nd floor. The 2nd floor switch does not appear to function. Identify function of the switch or eliminate. | 5/28/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Provide Phase 1 fire service operating instructions on the 1st floor. | 5/28/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall work with 24/7 support. | 12/18/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. | 10/25/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 9/2/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 9/2/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Need procedures for inspections and tests not described in A17.2. | 9/2/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 9/2/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made operable. Re-inspection required | 4/1/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.4 Plunger Gripper Testing | Yes | No | This unit has a plunger gripping device that is supposed to be tested every 5 years and has not been tested since 2018. 5 year full load testing required within 30 days. Re-inspection required | 4/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | This unit has an oil recovery system that returns oil that has leaked from the packing back to the pumping unit, this leakage is supposed to be monitored with a 5 gallon bucket. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | This unit has a oil recovery system that returns oil that has leaked from the packing back to the pumping unit, this leakage is supposed to be monitored with a 5 gallon bucket. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The car door operator cover is missing and shall be reinstalled. |