Inspection
Inspection Details
Equipment ID
8214
8214
Inspection Date
10/29/2018
10/29/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Richard Toeniskoetter
Richard Toeniskoetter
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
251e141a-f824-419d-b22a-5bea05e28303
251e141a-f824-419d-b22a-5bea05e28303
Location
St. Charles County Justice Center
301 N 2ND ST, SAINT CHARLES, MO
301 N 2ND ST, SAINT CHARLES, MO
Owner
St. Charles County Government Center
300 N 2ND ST RM 101, SAINT CHARLES, MO 63301-0273
300 N 2ND ST RM 101, SAINT CHARLES, MO 63301-0273
Billing
Attn: St. Charles County Government Center
300 N 2ND ST RM 101, SAINT CHARLES, MO 63301-0273
300 N 2ND ST RM 101, SAINT CHARLES, MO 63301-0273
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | x | Verify main and lighting fuses for proper rating and face out. | 7/12/2025 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | All FAID shall be tested. | 7/12/2025 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | x | Remove phone button/communication loss panel @ 2. | 7/12/2025 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Emergency power shall be tested. | 7/12/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Machine room shall have at least 1 GFCI. | 7/12/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine room lighting shall work and shall be at least 19fc. | 7/12/2025 | |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | x | Install proper MOD/Alteration data tag. | 7/12/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | x | Label all interface cabinets with description of operation in the machine room. | 7/12/2025 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | x | Remove phone button/communication loss panel @ 2. (To be re-inspected at completion of MOD on SID 8215) | 10/7/2025 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Emergency power shall be tested. (To be re-inspected at completion of MOD on SID 8215) | 10/7/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Machine room shall have at least 1 GFCI. (To be re-inspected at completion of MOD on SID 8215) | 10/7/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine room lighting shall work and shall be at least 19fc. (To be re-inspected at completion of MOD on SID 8215) | 10/7/2025 | |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | x | Install proper MOD/Alteration data tag. (To be re-inspected at completion of MOD on SID 8215) | 10/7/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | x | Label all interface cabinets with description of operation in the machine room. (To be re-inspected at completion of MOD on SID 8215) | 10/7/2025 |