Inspection
Inspection Details
Equipment ID
15006
15006
Inspection Date
3/1/2024
3/1/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Christopher McCarty
Christopher McCarty
Relief Valve Pressure
320
320
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
20/20
20/20
External ID
d1b9d15b-9b34-4333-a7e4-3ad26d3d5338
d1b9d15b-9b34-4333-a7e4-3ad26d3d5338
Location
Adams Elementary
1311 Tower Grove Ave, St. Louis, MO
Phone: (660) 646-5436
1311 Tower Grove Ave, St. Louis, MO
Phone: (660) 646-5436
Owner
Attn: Anthony Graphenreed
St. Louis Board of Education
801 N 11th St, St. Louis, MO 63101
Phone: (314) 535-2500
Email: Anthony.Graphenreed@slps.org
St. Louis Board of Education
801 N 11th St, St. Louis, MO 63101
Phone: (314) 535-2500
Email: Anthony.Graphenreed@slps.org
Billing
Attn: Cardinal Elevator
Cardinal Elevator
2851 Barrett Station Rd, St. Louis, MO 63021
Phone: (314) 939-9222
Email: lisa@cardinalelevator.com
Cardinal Elevator
2851 Barrett Station Rd, St. Louis, MO 63021
Phone: (314) 939-9222
Email: lisa@cardinalelevator.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Phase 2 Firemans return call cancel does not operate. | 7/18/2018 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Machine room shall not be used to store non-elevator related materials. | 10/26/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency lighting is not operational. | 10/26/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) | Yes | Yes | Car call cancel does not function on Phase 2 fire service. | 7/31/2019 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The machine room shall not be used for the storage of non-elevator related items. | 10/26/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The elevator pit shall be kept clean and dry. | 10/26/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The machine room shall not be used for the storage of non-elevator related items. | 10/26/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | There were no keys on site to test fire service. Keys shall be kept on site and fire service shall be tested. | 10/20/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Remove all non-elevator related items from the elevator machine room. | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve and is due for a category 5 test. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Emergency battery lowering shall be operational. | 1/30/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit sump shall have a cover in place. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)9 | No | No | Unable to check in car stop switch upon Phase I recall,no key. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unit not running at the time of inspection. |