Inspection
Inspection Details
Equipment ID
24515
24515
Inspection Date
3/4/2024
3/4/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
18/23
18/23
External ID
520c0afd-2a54-42d2-bdd1-9fd9374d578b
520c0afd-2a54-42d2-bdd1-9fd9374d578b
Location
Aloft Hotels
4245 Duncan Ave, St. Louis, MO
Phone: (000) 000-0000
4245 Duncan Ave, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Kathy Prainito
Midas Cortex, LLC
1804 Borman Circle Dr, St. Louis, MO 63146
Phone: (314) 991-1158
Email: KPrainito@midashospitality.com
Midas Cortex, LLC
1804 Borman Circle Dr, St. Louis, MO 63146
Phone: (314) 991-1158
Email: KPrainito@midashospitality.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | x | Seal all penetrations in the hoistway. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | All phases of fire service shall be tested. | 5/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | x | Finish the installation of the sump pump and cover. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | x | Finish construction of the elevator lobby and mount all fixtures and signage. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | x | Install lighting (19 ftc) in overhead machine space with switch and GFCI. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | x | Install lighting (10 ftc) in the pit with switch and GFCI. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 8.11.2.1.1(d) | x | Finish the elevator floor. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 8.11.2.1.1(d) | x | Finish grouting the sills. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The emergency lighting and alarm shall be tested. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Check for proper operation of the emergency phone. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | x | Install all electrical covers. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | x | Number the hoistway doors. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | x | Label disconnects for feed source. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | x | Check hoistway access. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | The penetrations in the overhead shall be sealed. | 5/27/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | The emergency power fixture at the egress floor for this car shall be removed. This car does not operate under emergency power. | 5/27/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | The powered hoistway vent in the overhead shall automatically open upon detection of smoke in the elevator lobbies or hoistway, and upon power failure. | 5/27/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | The powered hoistway vent in the overhead shall be sealed with masonry or other approved solid materials. | 5/27/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 4/5/2021 | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(b)(1) | Remove prints, maintenance records etc from top of the car | 9/21/2022 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | Perform monthly fire service and document on log in machine room | 9/21/2022 | ||
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Perform monthly fire service and document on log in machine room along with a maintenance control paln | 3/3/2023 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service and document on log in machine room | 3/18/2024 |