Inspection
Inspection Details
Equipment ID
6518
6518
Inspection Date
2/16/2024
2/16/2024
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
John Ryan
John Ryan
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
335779d5-1753-4f3f-80c9-3daae38ef78c
335779d5-1753-4f3f-80c9-3daae38ef78c
Location
FDA St. Louis Labratory
645 S Newstead Ave, St. Louis, MO
Phone: (314) 655-5818
645 S Newstead Ave, St. Louis, MO
Phone: (314) 655-5818
Owner
Attn: Kelly Perkins
St. Louis GSA FDA, LLC c/o Colliers International Asset Services, LLC
PO Box 13470, Richmond, VA 23225
Phone: (804) 495-7601
Alt Phone: (804) 320-5500
Fax: (804) 320-4839
Email: kelly.perkins@colliers.com
St. Louis GSA FDA, LLC c/o Colliers International Asset Services, LLC
PO Box 13470, Richmond, VA 23225
Phone: (804) 495-7601
Alt Phone: (804) 320-5500
Fax: (804) 320-4839
Email: kelly.perkins@colliers.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Car door and hoistway doors are dragging against sills and will not open fully adjust doors | 9/3/2019 |
| conversion | conversion | n/a | No | No | Elevator pit full of water clean elevator pit | 9/3/2019 |
| conversion | conversion | n/a | No | No | Replace missing hoistway door pickup rollers. | 9/3/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Building under renovation. Landing initiating devices (smokes) disconnected and/or removed. Replace, connect, and test all landing initiating devices. | 1/24/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit light inoperative. Repair. | 9/3/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove standing water from pit. | 9/3/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car top light inoperative. Repair. | 9/3/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)14 | No | No | Repair hole in hoistway shaft liner, second landing. | 9/3/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light inoperative. Repair. | 1/24/2020 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | Cab emergency stop switch toggle disconnected from alarm bell. | 1/24/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove standing water in pit. | 9/9/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light inoperative. | 9/9/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)14 | No | No | Repair hole in hoistway shaft liner. Second floor. | 9/9/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light inoperative. | 10/30/2020 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | Emergency stop toggle disconnected from alarm bell. | 10/30/2020 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)6 | No | No | Replace worn out guide shoes on elevator car top | 11/18/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean elevator pit from oil & debris | 11/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean dirt from elevator car top | 11/18/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | When hoistway doors are closed and in the locked position, the hoistway doors at the furthest point from the interlock can be opened 2 1/2 inches. Adjust / repair doors to open a maximum of 1 inch. | 11/18/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell in elevator cab does not work on battery backup power, needs repaired. Re-inspection required | 11/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Need to clean dirt from elevator car top | 11/18/2025 |