Inspection
Inspection Details
Equipment ID
22474
22474
Inspection Date
10/1/2018
10/1/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Rick Buttice
Rick Buttice
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
15ed920f-47e0-44e0-b97d-0a2b63a5e9e3
15ed920f-47e0-44e0-b97d-0a2b63a5e9e3
Location
West Pine Lofts, LLC
4050 W PINE BLVD, SAINT LOUIS, MO
4050 W PINE BLVD, SAINT LOUIS, MO
Owner
West Pine Lofts, LLC
150 E BROAD ST STE 200, COLUMBUS, OH 43215-3644
150 E BROAD ST STE 200, COLUMBUS, OH 43215-3644
Billing
Attn: West Pine Lofts, LLC
4050 W PINE BLVD, SAINT LOUIS, MO 63108-3289
4050 W PINE BLVD, SAINT LOUIS, MO 63108-3289
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | In cab emergency telephone shall work. | 10/1/2018 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Rescue plan is missing. (This item is for notification purposes for future violation in 2022) | 1/20/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be displayed in the elevator machine room. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 7/20/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car telephone shall be operational. Note: this was also a violation last year that was not corrected as of 7/20/2023. The phone shall be made operational in 14 days or less or the elevator will be red tagged. | 7/31/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | The machine room temperature shall be kept within the manufacturers recommended range. Note: The air conditioning in the machine room is not working. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an overspeed valve. Based on the installation date of 2015, a category 5 test will be due in 2025. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Fire service testing log shall be documented monthly. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | x | This elevator is equipped with an overspeed valve. Based on the installation date of 2015, a category 5 test will be due in 2025. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.30 - Hydraulic Power Unit | 3.24 | x | The pumping unit belts shall be adjusted so they do not slip under load. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 2.14.1.5 | x | Cartop emergency exit switch has been rendered inoperative (chain is detached from bracket). | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | x | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | x | The machine room temperature shall be kept within the manufacturers recommended range. Note: The air conditioning in the machine room is not working. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | x | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/20/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | x | Cartop shall be kept free of excess debris/dirt/lint. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | x | Machine room lighting needs to be repaired. One or more bulbs are not working. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | x | Sump pump has been rendered inoperative. Repair as needed. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | x | This elevator is equipped with an overspeed valve. Based on the installation date of 2015, a category 5 test is due. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.30 - Hydraulic Power Unit | 3.24 | x | The pumping unit belts shall be adjusted so they do not slip under load. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 2.14.1.5 | x | Cartop emergency exit switch has been rendered inoperative (chain is detached from bracket). | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | x | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | x | The machine room temperature shall be kept within the manufacturers recommended range. Note: The air conditioning in the machine room is not working. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | x | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | x | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | x | Cartop shall be kept free of excess debris/dirt/lint. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | x | Machine room lighting needs to be repaired. One or more bulbs are not working. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | x | Sump pump has been rendered inoperative. Repair as needed. |