Inspection
Inspection Details
Equipment ID
8596
8596
Inspection Date
2/27/2024
2/27/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
500
500
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
5ef07ce6-42ec-4ca6-a87f-73c830f56078
5ef07ce6-42ec-4ca6-a87f-73c830f56078
Location
Schnucks-Corporate Office
11420 LACKLAND RD, SAINT LOUIS, MO
Phone: (314) 994-4771
11420 LACKLAND RD, SAINT LOUIS, MO
Phone: (314) 994-4771
Owner
Attn: Alice Powderly
Schnucks Corporate
11420 Lackland Rd, St. Louis, MO 63146
Phone: (314) 994-4274
Email: jeheuermann@schnucks.com
Schnucks Corporate
11420 Lackland Rd, St. Louis, MO 63146
Phone: (314) 994-4274
Email: jeheuermann@schnucks.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Replace the missing ceiling tiles in the machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. | |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | A pit ladder is required. (This unit shares a hoistway/pit with another unit. There is a pit ladder for the other unit). | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | A light switch is required in the pit. This unit shares a hoistway/pit with another unit. There is a light switch near the other elevator access door. A light switch accessible from the access door shall be provided or the existing switch shall be re-located so that is accessible from both hoistway entrances. The light switch shall be independently accessible from both entrances. | |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | The pit sump pump shall be covered flush with the pit floor. The cover shall consist of a noncombustible material. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The tops of cars shall be kept free of oil, water, dirt, and rubbish. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be clean and dry. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. |