Inspection
Inspection Details
Equipment ID
15115
15115
Inspection Date
2/21/2024
2/21/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
NA
NA
External ID
baa1bfe4-9126-44c8-8a36-fd00ecedfb53
baa1bfe4-9126-44c8-8a36-fd00ecedfb53
Location
Hilton Hotel- STL
400 Olive St, St. Louis, MO
Phone: (000) 000-0000
400 Olive St, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Ruth M. Fulton
RB STL ARCH, LLC
4124 Worth Avenue, Columbus, OH 43219
Phone: (614) 246-2577
Email: rmfulton@rockbridgecapital.com
RB STL ARCH, LLC
4124 Worth Avenue, Columbus, OH 43219
Phone: (614) 246-2577
Email: rmfulton@rockbridgecapital.com
Billing
Attn: The PENNYWELL - STL Downtown at the Arch
The PENNYWELL - STL Downtown at the Arch
400 Olive St, St. Louis, MO 63102
Phone: (314) 436-0002
Email: Zachary.Sporbert@hilton.com
The PENNYWELL - STL Downtown at the Arch
400 Olive St, St. Louis, MO 63102
Phone: (314) 436-0002
Email: Zachary.Sporbert@hilton.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit | 6/15/2024 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 8.6.4.7 Cleaning of Hoistways | No | No | Remove excess lint from seismic wires 2.1.1.1.1 | 6/15/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace hoist belts - rouging | 2/23/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 6/15/2024 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | No | No | Provide lighting in machine space top of hoistway 2.7.6.3.2(c) | 6/15/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean Pit | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove excess lint from seismic wires in the hoistway | 6/15/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace hoist belts (red rouge) WITHIN 30 DAYS | 1/18/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide lighting in machine space top of hoistway | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top | 6/15/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | MRL belts, clean pit where written up on last years inspections and no action has been taken 30 day maximum to correct these violations. | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove excess lint from seismic wires in the hoistway | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide lighting in machine room space top of hoistway | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting at top of hoistway failed. Reinspection is required. Building management is currently getting bids for lighting at top of the hoistway and extension has been granted for 30 days as of the date of this report. | 6/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | PERFORM MONTHLY FIRE SERVICE TEST AND DOCUMENT ON THE LOG POSTED IN THE MACHINE ROOM | 8/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM | 8/22/2025 |