Inspection
Inspection Details
Equipment ID
8597
8597
Inspection Date
2/27/2024
2/27/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
340
340
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
4be12bd6-03a5-49b9-a3df-57df97bb3428
4be12bd6-03a5-49b9-a3df-57df97bb3428
Location
Schnucks-Corporate Office
11420 LACKLAND RD, SAINT LOUIS, MO
Phone: (314) 994-4771
11420 LACKLAND RD, SAINT LOUIS, MO
Phone: (314) 994-4771
Owner
Attn: Alice Powderly
Schnucks Corporate
11420 Lackland Rd, St. Louis, MO 63146
Phone: (314) 994-4274
Email: jeheuermann@schnucks.com
Schnucks Corporate
11420 Lackland Rd, St. Louis, MO 63146
Phone: (314) 994-4274
Email: jeheuermann@schnucks.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 10/7/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.3.2.2 Cylinders Test shall be performed | Yes | No | The car goes onto the stop ring before it reaches the top floor level, and therefore doesn't meet the requirements of A17.1 - 3.18 | 12/23/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve (Red Tag) | Yes | Yes | While attempting to witness the category 5 testing of the overspeed valve, the elevator was unable to hold the rated load of 2500 lbs. The elevator is red tagged and the category 5 overspeed valve test still needs to be completed. | 7/26/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Replace the missing ceiling tiles in the machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. | |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | The pit sump pump shall be covered flush with the pit floor. The cover shall consist of a noncombustible material. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The tops of cars shall be kept free of oil, water, dirt, and rubbish. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | When the auxiliary lowering operation has been initiated, the car shall descend directly to the lowest landing and open the doors. | 9/30/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | All pits shall be kept clean and dry. |