Inspection
Inspection Details
Equipment ID
23882
23882
Inspection Date
2/22/2024
2/22/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
NA
NA
Slide
3" net @ 150fpm
3" net @ 150fpm
Governor Rope Pull
35/205
35/205
Door Closing Force
18F/20R
18F/20R
External ID
c5f18a02-74a4-46d6-932a-36d16aec6a2e
c5f18a02-74a4-46d6-932a-36d16aec6a2e
Location
Tru Hotel
333 Camelback Rd, St. Charles, MO
Phone: (000) 000-0000
333 Camelback Rd, St. Charles, MO
Phone: (000) 000-0000
Owner
Attn: St Charles Hotel Associates, LLC
St Charles Hotel Associates, LLC
808 US Hwy 18 E, Clear Lake, IA 50428
Phone: (636) 669-2500
Email: ganderson@kinseth.com
St Charles Hotel Associates, LLC
808 US Hwy 18 E, Clear Lake, IA 50428
Phone: (636) 669-2500
Email: ganderson@kinseth.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | In car emergency telephone shall work. | 6/5/2018 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Seal all penetrations in the hoistway. | 6/5/2018 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | A fire service testing log shall be kept on-site. | 9/3/2019 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide MCP. | 9/3/2019 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display current state operating certificate. | 9/3/2019 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/11/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/13/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | Subsequent to the first stop of the car following the opening of the tail switch tension switch, the car shall remain inoperative until the switch is manually reset. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 2.18.5 | The governor rope shall be tagged as specified by A17.1 2005 - 2.18.5.3 | 6/13/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | The suspension ropes shall be tagged as specified by A17.1 2005 - 2.20.2.2 | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | x | There are fire guides missing from some hoistway doors. | 2/22/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 2/22/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. Note: Building personnel attempted to start the generator and transfer power, but we unsuccessful. | 3/25/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. |