Inspection
Inspection Details
Equipment ID
15717
15717
Inspection Date
10/25/2018
10/25/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
80/450
80/450
Door Closing Force
24
24
External ID
1e871a92-aee2-44e0-9c88-8679cbc3b2fe
1e871a92-aee2-44e0-9c88-8679cbc3b2fe
Location
Metro Link Headquarters
707 N 1ST ST, SAINT LOUIS, MO
707 N 1ST ST, SAINT LOUIS, MO
Owner
Metro Link Headquarters
707 NORTH 1ST ST-MAILSTOP-460, ST. LOUIS, MO 63102
707 NORTH 1ST ST-MAILSTOP-460, ST. LOUIS, MO 63102
Billing
Attn: Metro/STL
707 N 1ST ST, SAINT LOUIS, MO 63102-2505
707 N 1ST ST, SAINT LOUIS, MO 63102-2505
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | No | No | Car door restrictor does not work and shall be repaired. | 1/4/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car top light does not work and shall be repaired. | 1/4/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | High voltage (110V) wiring on car top shall be enclosed in conduit. | 1/4/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Hoistway duct covers shall be installed. | 1/4/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Suspension rope data tags shall be installed. | 1/4/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not work and shall be repaired. | 1/4/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Pit sump pump cover shall be installed flush with the pit floor. | 1/4/2019 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Weight related testing of safeties, buffers, and machine brakes shall be completed. | 11/8/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The door restrictor shall be operational. | 9/22/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be posted in the machine room in a non-combustible frame. | 10/26/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | A counterweight guard shall be installed. | 10/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency light shall be operational. | 9/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The alarm bell shall operate on auxiliary power. | 9/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 9/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Yes | Yes | Fire service phase 1 instructions shall be posted at the hall key switch, and fire service phase 2 instructions shall be posted in the car. | 9/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Fire service phase 1 & phase 2 key switches shall be legible. | 9/22/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-locking and self-closing. | 10/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The machine room fire extinguisher shall be tagged to verify that the extinguisher is current. | 10/26/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Traveling cables in the machine room shall be enclosed in wireway. | 10/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 12/1/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current ABC type fire extinguisher shall be provided in the machine room. |