Inspection
Inspection Details
Equipment ID
10392
10392
Inspection Date
3/6/2024
3/6/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
17
17
External ID
80dd3a02-2bf7-4c00-9ada-cc65ab9502ac
80dd3a02-2bf7-4c00-9ada-cc65ab9502ac
Location
Courtyard by Marriott
827 Washington Ave, St. Louis, MO
Phone: (314) 231-7560
827 Washington Ave, St. Louis, MO
Phone: (314) 231-7560
Owner
Attn: Courtyard by Marriott
Courtyard by Marriott
827 Washington Ave, St. Louis, MO 63101
Phone: (314) 418-5840
Email: rodney.anderson@marriott.com
Courtyard by Marriott
827 Washington Ave, St. Louis, MO 63101
Phone: (314) 418-5840
Email: rodney.anderson@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | 1206.2c - Clean the car top. | 10/8/2019 | ||
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide a code compliant MCP including onsite documents. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | The car door restrictor shall be operational. | 2/22/2022 | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | The car top shall be kept clean. Clean the car top. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Pits shall be kept clean. Clean the pit. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The phone is hard to hear due to static. Take corrective action as needed. | 2/22/2022 | |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 1001.2(b)(11) | Label the disconnects with the location, source, and breaker numbers of the panel from which it is fed. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 2/22/2022 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The phone is hard to hear due to static. Take corrective action as needed. | 1/24/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | The emergency power indicator light shall activate when unit is operating on emergency power. | 7/10/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | The emergency power indicator light shall activate when unit is operating on emergency power. | 7/10/2024 | ||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | The standby/emergency power indicator light at the egress floor shall illuminate when on emergency power operation. | 3/6/2024 | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | The car top is dirty. Clean the car top. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | MCP hasn't been updated since 2022. | |||
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | Cartop shall be kept free of excess debris/dirt/lint. | |||
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.2 | Machine room lighting needs to be repaired, 1 or more bulbs not working. | |||
| A17.1-1996 : Elevators | 3.22 - Wire rope fastening and hitch plate | 212 | .9e(4) - Hoist Rope Tail retaining clips shall be properly spaced. Counterweight side. | |||
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 110 | 110.11f(3) - Hoistway door gib fire tabs shall be engaged into the guideway(sill) : 17 & 23rd floor | |||
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | There is a large amount of "Rope Dust" on the floor by the machine. Hoist Ropes appear dry and showing “rouge”. Ropes shall be cleaned and lubricated per OEM recommendations. |