Inspection
Inspection Details
Equipment ID
16224
16224
Inspection Date
2/20/2024
2/20/2024
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Michael Beachner
Michael Beachner
Relief Valve Pressure
n/a
n/a
Slide
instant
instant
Governor Rope Pull
n/a
n/a
Door Closing Force
18
18
External ID
b53fffcf-3111-43be-8926-f76ec73dcc09
b53fffcf-3111-43be-8926-f76ec73dcc09
Location
KC Chiefs Training Facility
1 Arrowhead Dr, Kansas City, MO
Phone: (816) 918-5233
1 Arrowhead Dr, Kansas City, MO
Phone: (816) 918-5233
Owner
Attn: John Reardon
Jackson County Sports Authority
1 Arrowhead Dr, Kansas City, MO 64129
Phone: (816) 920-4962
Alt Phone: (816) 920-4736
Email: JReardon@Chiefs.nfl.com
Jackson County Sports Authority
1 Arrowhead Dr, Kansas City, MO 64129
Phone: (816) 920-4962
Alt Phone: (816) 920-4736
Email: JReardon@Chiefs.nfl.com
Billing
Attn: Jackson County Sports Authority
Jackson County Sports Authority
1 Arrowhead Dr, Kansas City, MO 64129
Phone: (816) 920-4962
Email: tidel@chiefs.nfl.com
Jackson County Sports Authority
1 Arrowhead Dr, Kansas City, MO 64129
Phone: (816) 920-4962
Email: tidel@chiefs.nfl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.3.4 | Yes | No | 125% brake test not performed, did not have weights | 2/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.3.1 | Yes | No | 5 year governor test not performed | 2/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.29 - Car and counterweight safeties | 8.11.2.3.1 | Yes | Yes | 5 year safety slide not performed, did not have test weights | 2/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | perform monthly fire service test and post log in the machine room | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the copy of the state operating certificate in the machine room is to be updated every year | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | the monthly fire service test log is not being filled out | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(f) | No | No | replace burnt out machine room light bulbs | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(j) | No | No | the machine room fire extinguisher was last checked in 2019 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone went strait to busy signal | 2/15/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not connect to stadium security | 2/13/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service test log is not being filled out | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate posted in the machine room is to be updated annually, the one in the machine room is from 2015 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | do not store non elevator related material in the machine room | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate posted in the machine room expired in 2015, update with the current certificate when received from the state annually | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone was not answered, verify the phone line, verify the number dialed, reinspection required when fixed | 2/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating in the machine expired in 2015, update with a current operating certificate annually | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating in the machine expired in 2015, update with a current operating certificate annually | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Do not store non-Elevator related items in the elevator machine room |