Inspection
Inspection Details
Equipment ID
14509
14509
Inspection Date
3/18/2024
3/18/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Bryan Henson
Bryan Henson
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
F-22/R=21
F-22/R=21
External ID
11f212d4-35fd-4ef7-99f4-72949e1da8ee
11f212d4-35fd-4ef7-99f4-72949e1da8ee
Location
Nevada Regional Medical Center
800 S Ash St, Nevada, MO
Phone: (417) 667-3355
800 S Ash St, Nevada, MO
Phone: (417) 667-3355
Owner
Attn: Michael Holder
Nevada Regional Medical Center
800 S Ash St, Nevada, MO 64772
Phone: (417) 448-3740
Email: mholder@nrmchealth.com
Nevada Regional Medical Center
800 S Ash St, Nevada, MO 64772
Phone: (417) 448-3740
Email: mholder@nrmchealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | needs record of oil usage | 2/21/2020 |
| conversion | conversion | n/a | No | No | rear restrictor needs adjusted or repairerd | 2/21/2020 |
| conversion | conversion | n/a | No | No | needs maintance record on site | 2/21/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | 8.11.3.1.1(f) emergency light needs battery | 2/21/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | needs current certificarte posted | 2/21/2020 |
| A17.1-1996 : Elevators | 2.35 - Supply Line and Shutoff Valve | 303 | No | No | Shutoff valve in machine room will not close--needs replaced | 3/23/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4 Instructions for Locating Maintenance Records | No | No | No Records | 1/11/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Post monthly fire service log in machine room | 1/23/2024 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Must perform Category 5 test on overspeed valve on or before next annual insp. 8.6.5.16.5 | 1/23/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current operating Cert. in Mach Room 5.100(2) | 1/23/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make Emergency Phone Operable. 8.6.4.15 | 9/18/2025 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | Must perform Cat. 5 Full load test/insp. for Overspeed Valve within next 90 days. 8.6.5.16.5 | 9/18/2025 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | No | Must repair/replace Jack Packing Gland to limit oil loss. (5 gal pit bucket was full, noted it had been emptied in the last 45 days). 8.6.5.5 | 5/29/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit must be kept free of Oil. 8.6.4.7 | 5/29/2026 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5 Gland Packing and Seals | Yes | No | Must repace jack packing gland to limit oil loss. 8.6.5.5 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit must be kept free of oil. 5.1 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emergency phone operable. 8.6.4.15 |