Inspection
Inspection Details
Equipment ID
10176
10176
Inspection Date
2/27/2024
2/27/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
Missing
Missing
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
19
19
External ID
fc97de88-ef0d-48a7-ab79-59b310072b35
fc97de88-ef0d-48a7-ab79-59b310072b35
Location
Hidden Lake Care Center
11732 Hidden Lake Dr, St. Louis, MO
Phone: (314) 355-5153
11732 Hidden Lake Dr, St. Louis, MO
Phone: (314) 355-5153
Owner
Attn: Michael Barth
Hidden Lake Care Center
11750 Hidden Lake Dr, St. Louis, MO 63138
Phone: (000) 000-0000
Email: mbarth@estatesofhiddenlake.com
Hidden Lake Care Center
11750 Hidden Lake Dr, St. Louis, MO 63138
Phone: (000) 000-0000
Email: mbarth@estatesofhiddenlake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 11/21/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational with 24/7 support. | 11/4/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | The car top emergency exit shall be properly attached with a means to prevent falling, i.e. chain/wire. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Observed hydraulic oil in tank to be "milky". The oil appears to be contaminated. Verify the condition of the hydraulic oil and replace as needed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lights shall be guarded. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 2/27/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | The code data plate required by A17.1 2016 8.9 shall be provided in plain view, securely attached to each main line disconnect or controller. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | The data on the MCP shall be filled out as required by A17.1 2016 8.6.1.4.1(a)(3). | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | The car operating panel has a hole which was formerly used for a pushbutton or key-switch. This hole is presently covered with paper and tape. This hole shall be properly covered to prevent accidental contact with the live voltage inside the panel. | 2/27/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | Yes | No | The car-top emergency exit shall be secured to prevent it from falling down the hoistway. (2nd Notice) Re-Inspection required | 2/27/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Relief pressure must be tested. |