Inspection
Inspection Details
Equipment ID
21347
21347
Inspection Date
10/26/2017
10/26/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Regions Bank
10449 St. Charles Rock Rd, St. Ann, MO
Phone: (314) 427-4000
10449 St. Charles Rock Rd, St. Ann, MO
Phone: (314) 427-4000
Owner
North Port Building
5988 Mid rivers Mall Dr, St Charles, MO 63304
5988 Mid rivers Mall Dr, St Charles, MO 63304
Billing
Attn: Regions Bank
10449 St Charles Rock Rd, , MO 63047
10449 St Charles Rock Rd, , MO 63047
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Test not complete. Car failed 125% brake test. Also, car was not running contract speed. | |
| conversion | conversion | n/a | No | No | Per Larry Watson, he gave Kone two weeks to complete repairs. | |
| conversion | conversion | n/a | No | No | Test not complete. Car failed 125% brake test. Also, car was not running contract speed. | |
| conversion | conversion | n/a | No | No | Per Larry Watson, he gave Kone two weeks to complete repairs. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car traveling at 16% of contract speed. Determine cause and perform full load safety test for proper slide. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 3/2/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide MCP | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Expired | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Car speed is rated at 200 fpm. Up full load =70fpm, down=150. Provide car to run at contract speed. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Car safety not tested. Provide car to run at contract speed. Cat 5 safety test required. Record slide. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide machine room door to be self locking. |