Inspection
Inspection Details
Equipment ID
15153
15153
Inspection Date
3/11/2024
3/11/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
e28b6408-4fd9-431a-be60-743e5e3e963b
e28b6408-4fd9-431a-be60-743e5e3e963b
Location
City View Apts- Bldg 10
111 N 15th St, Bldg 10, St. Louis, MO
Phone: (314) 588-1177
111 N 15th St, Bldg 10, St. Louis, MO
Phone: (314) 588-1177
Owner
Attn: Rock Rose City View SPE LLC DBA Gateway at City Park
c/o Blue Magma Residential, LLC
13095 Telecom Parkway N, Tampa, FL 33637
Phone: (813) 620-0800
Email: amobley@bmresidential.com
c/o Blue Magma Residential, LLC
13095 Telecom Parkway N, Tampa, FL 33637
Phone: (813) 620-0800
Email: amobley@bmresidential.com
Billing
Attn: Blue Magma Residential, Gateway at City Park Apartments
Blue Magma Residential, Gateway at City Park Apartments
110 N 17th St, St. Louis, MO 63103
Phone: (314) 588-1177
Email: lcapehart@bmresidential.com
Blue Magma Residential, Gateway at City Park Apartments
110 N 17th St, St. Louis, MO 63103
Phone: (314) 588-1177
Email: lcapehart@bmresidential.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | The hoist ropes need replacing. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | Tighten the upthrust on the 9th floor hoistway door. | 10/19/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Adjust the door restrictor for proper operation. | 10/19/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.20.2 | No | No | A rope data tag is required on the suspension ropes. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 2.18.5 | No | No | 2.18.5.3 - A rope data tag is required on the governor rope. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 2.21 | No | No | 2.21.1.2 - Secure counterweights in the frame. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.1 | No | No | 2.29.1(g) - Label the crosshead with the elevator number. | 1/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. Violation originally cited on 10/20/22 and still not corrected. Violations shall be corrected within 14 days or elevator will be red tagged and locked out of service. | 3/11/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | The fire extinguisher is expired. A current tested and tagged ABC type fire extinguisher shall be provided in the machine room. | 1/21/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | A clear path shall be provided to the machine room. Remove paint, supplies, etc. and make a clear path to machine room. | 1/21/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational (3rd Notice). Per Chief Inspector Gus Guadamuz, 14 days to fix phones or individual units will start being taken out of service. | 8/27/2024 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Handrails shall be provided on all nonaccess walls. |