Inspection
Inspection Details
Equipment ID
6074
6074
Inspection Date
3/29/2024
3/29/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
28
28
External ID
3b354f52-935d-45ff-9053-f9959e58b560
3b354f52-935d-45ff-9053-f9959e58b560
Location
Arch Hotel Project Owner LLC
315 Chestnut St, St. Louis, MO
Phone: (314) 655-1234
315 Chestnut St, St. Louis, MO
Phone: (314) 655-1234
Owner
Attn: Hank Hermes, Director of Engineering
Hyatt Regency St Louis at the Arch
N 4th St at Chestnut St, St. Louis, MO 63102
Phone: (314) 294-4660
Alt Phone: (314) 393-2435
Email: hank.hermes@hyatt.com
Hyatt Regency St Louis at the Arch
N 4th St at Chestnut St, St. Louis, MO 63102
Phone: (314) 294-4660
Alt Phone: (314) 393-2435
Email: hank.hermes@hyatt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Install missing duct covers in hoistway | 5/1/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.3.3.3 Runby & Clearances After Reroping or shortening | Yes | No | Counterweight runby is 0". Shorten hoisting cables to maintain 6" runby. | 5/27/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab is not working. Re-inspection required | 11/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean cartop | 6/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light and alarm does not work on emergency power. | 4/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | 2 top counterweight guide rollers are deteriorated. Replace same | 6/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing hoistway door gibs at 4th and 1st floor | 6/4/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | Replace missing hoistway door safety retainers at 1st floor | 6/4/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are undersized and showing rouge. Replace ropes within 60 days. | 4/26/2023 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 2.19.2 | Yes | Yes | Emergency brake failed unintended movement testing. RED TAGGED. Repair and reinspect | 4/26/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform fire service testing to complete inspection | 4/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean elevator car top | 6/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Elevator cab emergency light does not work | 3/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace damaged counterweight rollers. top | 6/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing hoistway door safety retainers, 1st floor | 6/4/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are undersized and showing rouge. Replace by 6/4/23 | 3/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing hoistway door gibbs, 1st and 4th floors | 6/4/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 6/4/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace missing duct cover in hoistway at first floor | 6/4/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unit has emergency generator backup power, which needs to be scheduled and tested to complete inspection. Re-inspection required | 5/13/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Elevator cab emergency lights do not work. Re-inspection required | 5/13/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace damaged counterweight rollers | 6/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing hoistway door safety retainers at 1st floor | 6/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing hoistway door gibbs at 1st & 4th floors | 6/4/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | This elevator is due for category 5 testing in 2025. Testing was scheduled for this date but hotel management asked that it be delayed. | 6/4/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/4/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Smoke on 3rd floor shall recall elevator to main fire floor | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Heat in top of hoistway shall shunt elevator |