Inspection
Inspection Details
Equipment ID
11167
11167
Inspection Date
3/21/2024
3/21/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
fb6c4b78-b04b-47f3-9828-468863260014
fb6c4b78-b04b-47f3-9828-468863260014
Location
Pierre Laclede Center
7733 Forsyth Blvd, Clayton, MO
Phone: (314) 862-2432
7733 Forsyth Blvd, Clayton, MO
Phone: (314) 862-2432
Owner
Attn: LCP Forsyth Blvd Prop. Owner, LLC
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, CLAYTON, MO 63105
Phone: (314) 862-2432
Email: d_kasten@commonwealth.com
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, CLAYTON, MO 63105
Phone: (314) 862-2432
Email: d_kasten@commonwealth.com
Billing
Attn: LCP Forsyth Blvd Prop. Owner, LLC
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, SAINT LOUIS, MO 63105
Phone: (000) 000-0000
Email: dkasten@commonwealthcommercial.com
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, SAINT LOUIS, MO 63105
Phone: (000) 000-0000
Email: dkasten@commonwealthcommercial.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Schedule a full lad test of the emergency power system on elevators 1-8. | 4/23/2019 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | The emergency power shall be tested with 125% of capacity. | 7/28/2019 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | Yes | Replace Ropes on car #5 Car is out of service | 5/1/2020 |
| A17.1-1996 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 1001.2(b)(17) | Yes | No | The Machine need to have the bearings check. Runs really loud | 5/1/2020 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency/standby power operation of the elevators shall be operational. | 10/5/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/26/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service checklist are missing. | 4/26/2022 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor shall work at all floors. | 6/26/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/26/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete: Began annual & Cat 5 testing, remaining testing to be finished by another inspector. Items tested - Hoistway, door, gate, restrictor, cartop, pits, light, bell, phone, comp-sheave, ring & string, terminal limits. | 3/12/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. Dials out, but no answer. | 3/12/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired State operating certificate in the machine room. |