Inspection
Inspection Details
Equipment ID
9787
9787
Inspection Date
11/1/2018
11/1/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
William Gorden, Jr.
William Gorden, Jr.
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
771afc5d-a456-4edf-bffe-94d7020dc6c6
771afc5d-a456-4edf-bffe-94d7020dc6c6
Location
Edward Jones Dome
901 N BROADWAY, SAINT LOUIS, MO
901 N BROADWAY, SAINT LOUIS, MO
Owner
America's Center
701 CONVENTION PLZ, SAINT LOUIS, MO 63101-1275
701 CONVENTION PLZ, SAINT LOUIS, MO 63101-1275
Billing
Attn: America's Center
701 CONVENTION PLZ, SAINT LOUIS, MO 63101-1275
701 CONVENTION PLZ, SAINT LOUIS, MO 63101-1275
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean out pits top to bottom. | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Log in entries must be updated on Maintenance log. | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(A) | No | Yes | Brake torque failed. Minimum 125 - it's 110. Repair or replace brake. | 9/21/2021 |
| Missouri Minimum : Escalators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(3) Escalators Placed out of Service | Yes | Yes | Incomplete test - indexing needs to be completed. | 9/21/2021 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean out top and bottom pit area | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Update MCP | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(A) | No | Yes | Brake failed, unit red tagged and removed from service. Repair and retest | 9/21/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform step indexing to complete inspection. Re-inspection required | 7/23/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Bottom demarcation light does not work. Re-inspection required | 7/23/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Bottom demarcation light is not working. Re-inspection required | 3/31/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 3/31/2026 |