Inspection
Inspection Details
Equipment ID
9795
9795
Inspection Date
11/2/2018
11/2/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
f99e38c0-5be8-4056-a080-1d833e7681e9
f99e38c0-5be8-4056-a080-1d833e7681e9
Location
Edward Jones Dome
901 N BROADWAY, SAINT LOUIS, MO
901 N BROADWAY, SAINT LOUIS, MO
Owner
America's Center
701 CONVENTION PLZ, SAINT LOUIS, MO 63101-1275
701 CONVENTION PLZ, SAINT LOUIS, MO 63101-1275
Billing
Attn: America's Center
701 CONVENTION PLZ, SAINT LOUIS, MO 63101-1275
701 CONVENTION PLZ, SAINT LOUIS, MO 63101-1275
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Provide written maintenance control program to include wiring diagrams to be kept on site. | 6/4/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Perform unit clean down and repair seals causing oil leak on steps. | 6/4/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(E) | No | No | Top right comb plate has 2 missing teeth, needs replaced | 6/4/2026 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current certificate | 6/4/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.11.4.2.13 Escalator Handrail Safety Systems | Yes | No | Provide Category 1 testing.of handrail | 9/20/2022 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.3 Step/Skirt Performance Index | Yes | No | Provide Category 1 testing.of step/ skirt index | 9/20/2022 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(A) | Yes | No | Provide Category 1 testing.of brake torque. | 9/20/2022 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.4 Escalator Combplates | Yes | No | Provide Category 1 testing, lower center comb. | 9/20/2022 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.14 Escalator Entrance and Egress Ends | Yes | Yes | Screws broken off upper center comb plate during testing, unit removed from service. | 9/20/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 6/4/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Perform complete clean down to remove oil leaking from drive machine. | 6/4/2026 |
| MO Minimum : Elevators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | T(1) 704 Driving Machines and Sheaves | No | No | Need to replace leaking seal on drive machine. | 6/4/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(F) | No | No | Repair balustrade joint on right side to match up with adjacent panel | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unable to test brake torque because testing point is stripped. Repair or replace and re-inspect within 60 days | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Perform complete clean down to remove oil leaking from drive machine. | |
| MO Minimum : Elevators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | T(1) 704 Driving Machines and Sheaves | No | No | Need to replace leaking seal on drive machine. |