Inspection
Inspection Details
Equipment ID
13155
13155
Inspection Date
1/23/2018
1/23/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
Location
St. Luke's Plaza Apts
5616 Enright, St. Louis, MO
Phone: (314) 361-0418
5616 Enright, St. Louis, MO
Phone: (314) 361-0418
Owner
McCormack Baron Management
750 Olive St Suite 2500, ST Louis, MO 63101
750 Olive St Suite 2500, ST Louis, MO 63101
Billing
Attn: St. Luke's Plaza Apts
5602 Enright Ave, Ste 2, , MO 63112
5602 Enright Ave, Ste 2, , MO 63112
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 11/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency telephone shall be operational. Elevator was left in service due to being only unit in building. If phone or alarm bell is not corrected by 11/20/2020, the elevator will be shut down. | 11/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency alarm bell shall be operational. Elevator was left in service due to being only unit in building. If phone or alarm bell is not corrected by 11/20/2020, the elevator will be shut down. | 11/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency light and alarm bell shall be operational. | 12/17/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/4/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Debris shall be removed from the pit floor. | 1/4/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/4/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 1/4/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. |