Inspection
Inspection Details
Equipment ID
6750
6750
Inspection Date
11/5/2018
11/5/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Bryan Hesskamp
Bryan Hesskamp
Relief Valve Pressure
390
390
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
547d69af-8fd6-49f0-a3d5-41109b8d578b
547d69af-8fd6-49f0-a3d5-41109b8d578b
Location
Hampton Inn- Sunset Hills
1580 S KIRKWOOD RD, SAINT LOUIS, MO
1580 S KIRKWOOD RD, SAINT LOUIS, MO
Owner
Attn: Hampton Inn- Sunset Hills
Hampton Inn
1580 S KIRKWOOD RD, SAINT LOUIS, MO 63127-1013
Hampton Inn
1580 S KIRKWOOD RD, SAINT LOUIS, MO 63127-1013
Billing
Attn: Hampton Inn
Hampton Inn- Sunset Hills
1580 S KIRKWOOD RD, SAINT LOUIS, MO 63127-1013
Hampton Inn- Sunset Hills
1580 S KIRKWOOD RD, SAINT LOUIS, MO 63127-1013
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | 3. Hoistways and pits shall be kept free of dirt and rubbish and shall not be used for storage purposes. Pit needs to be cleaned. | 10/30/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | 2. Two-way communication means shall initiate a call for help and establish two-way communications. Two-way communications is not functioning, seems to have a busy signal. | 11/5/2018 |
| conversion | conversion | n/a | No | No | 1. Maintenance records shall document compliance with 8.6 of the Code and shall include records of maintenance, repairs, testing, etc. No records available for maintenance per code. | 10/30/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 12/13/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit needs to be cleaned. | 12/1/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Machine room needs to be cleaned. | 12/1/2020 |
| A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | No | No | Clean car top. | 12/1/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate needs to be posted in machine room. | 12/1/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | This elevator has an overspeed valve device installed that is not sealed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Overspeed valve shall be tested within 90 days. | 11/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 12/29/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | There is no signage for Firefighters Operation by the phase I key switch. Obtain the correct signage from the building code addition that this elevator was designed to meet. | 12/29/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | OSV needs to have full load test performed. Re-inspection required | 1/5/2023 |