Inspection
Inspection Details
Equipment ID
8900
8900
Inspection Date
10/11/2018
10/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Rick Buttice
Rick Buttice
Mechanic Name
Richard Rickermann
Richard Rickermann
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
0f83a497-ee56-4770-a4a6-dc475b371246
0f83a497-ee56-4770-a4a6-dc475b371246
Location
Town Place Suites- Fenton
1662 FENTON HILLS RD, FENTON, MO
1662 FENTON HILLS RD, FENTON, MO
Owner
Lakshmi Hospitality Group
445 HOTEL CIR S, SAN DIEGO, CA 92108-3402
445 HOTEL CIR S, SAN DIEGO, CA 92108-3402
Billing
Attn: Town Place Suites-Fenton
1662 FENTON HILLS RD, FENTON, MO 63026
1662 FENTON HILLS RD, FENTON, MO 63026
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 10/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The car door light ray shall be operational. | 10/28/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 10/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Electric photo eye re-opening device shall be operable. Re-Inspection Required (2nd Notice) | 3/7/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/30/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Access to the machine space shall maintained in a clear and unobstructed manner. There is debris on the floor of the room leading to the machine room and blocking access to it - including broken fluorescent bulbs. | 11/30/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. The machine room door is being blocked from closing due to an excessive amount of debris on the floor of the room leading to it. | 11/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. | 11/30/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light shall be operational. | 11/30/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lights shall be operational. | 11/30/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. |