Inspection
Inspection Details
Equipment ID
18316
18316
Inspection Date
3/28/2024
3/28/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
6facf5b1-4471-42c3-9e55-26c101adc9a1
6facf5b1-4471-42c3-9e55-26c101adc9a1
Location
Dickmann Building
3115 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 932-1159
3115 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 932-1159
Owner
Attn: GST Properties LLC
GST Properties LLC
3115 S Grand Blvd, Ste 300, St. Louis, MO 63118
Phone: (000) 000-0000
Email: mjghio@gmail.com
GST Properties LLC
3115 S Grand Blvd, Ste 300, St. Louis, MO 63118
Phone: (000) 000-0000
Email: mjghio@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - red tag | Yes | Yes | Governor jaws and rope shall be replaced, car safeties would not set. | 4/15/2019 |
| conversion | conversion | conversion - red tag | Yes | Yes | Cable on wind up drum is damaged and shall be replaced. | 4/15/2019 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Governor jaws and governor rope shall be replaced, car safeties would not set. | 5/22/2020 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Cable on wind up drum is damaged and shall be replaced. | 5/22/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/13/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | The holes in the overhead shall be sealed with approved solid material. | 6/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The material not necessary for the operation of the elevator, trash, and defective parts shall be removed from the machine room. | 6/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | The covers shall be installed on all electrical equipment in the machine room, including the controllers. | 6/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | The machines shall be numbered. | 6/13/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A monthly fire service testing log shall be posted and kept on-site. | 6/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A maintenance control program (MCP) shall be provided. | 6/13/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | Wiring running from controller 1 to controller 2 shall be enclosed in raceway or wireway. | 6/13/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Holes in the hoistway between floors 1 and 2 shall be sealed with approved solid materials. | 6/13/2023 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | The door close button shall be operational on firefighters Phase 2 operation. (Doors presently close with car call button, but not with door close button) - The installation year and adopted code at time of installation shall be confirmed to determine if this violation applies. | 3/3/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The emergency lighting shall be operational. | 3/3/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The alarm bell shall be operational on main and auxiliary power. | 3/3/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | An up to date, legible copy of the schematics shall be located in the machine room for each elevator. | 6/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current ABC type fire extinguisher shall be located in the machine room. | 6/13/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Door close button does not work on Phase II fire service. | 3/8/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be kept clean. Clean the car top. | 6/13/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | 6/13/2023 |