Inspection
Inspection Details
Equipment ID
16423
16423
Inspection Date
3/29/2024
3/29/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
405
405
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
3a4dc236-c967-4497-b303-04ea968cd51b
3a4dc236-c967-4497-b303-04ea968cd51b
Location
Centennial Commons at Heman Park
7210 OLIVE BLVD, UNIVERSITY CITY, MO
Phone: (314) 862-6767
7210 OLIVE BLVD, UNIVERSITY CITY, MO
Phone: (314) 862-6767
Owner
Attn: University City, City Hall
University City, City Hall
6801 Delmar Blvd, University City, MO 63130
Phone: (000) 000-0000
Email: dcarter@ucitymo.org
University City, City Hall
6801 Delmar Blvd, University City, MO 63130
Phone: (000) 000-0000
Email: dcarter@ucitymo.org
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 1/5/2023 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 1/5/2023 | ||
A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 1/5/2023 | ||
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 1/5/2023 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Clean the pit of oil. | 1/5/2023 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be displayed in the elevator machine room. | 3/29/2024 | ||
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | x | This elevator is equipped with an unsealed overspeed valve. A category 5 test is due. | 4/27/2023 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Battery lowering device does not work per code. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10. | 3/29/2024 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Clean the pit of dirt and debris. | 3/29/2024 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Two-way communication device shall work. | ||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Battery lowering shall work. Take corrective action and re-test. | ||
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Emergency lighting shall work. | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Fire service testing must be documented monthly. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | Machine room shall have GFCI outlet. Currently outlets occupied by other devices. |