Inspection
Inspection Details
Equipment ID
18873
18873
Inspection Date
4/3/2024
4/3/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
848969b7-df36-4b0c-b5ae-842e98b949f9
848969b7-df36-4b0c-b5ae-842e98b949f9
Location
Ninth Street Parking Garage
N 9th St at Olive St, St. Louis, MO
Phone: (314) 621-3858
N 9th St at Olive St, St. Louis, MO
Phone: (314) 621-3858
Owner
Attn: INTERAGENCY
Missouri Development Finance Board-INTERAGENCY
301 W High St, Rm 680, Jefferson City, MO 65101
Phone: (000) 000-0000
Missouri Development Finance Board-INTERAGENCY
301 W High St, Rm 680, Jefferson City, MO 65101
Phone: (000) 000-0000
Billing
Attn: Kenny Darragh
St. Louis Parking Co
1617 S 3rd St, St. Louis, MO 63104
Phone: (314) 241-7777 Ext: 103
Fax: (877) 310-9169
Email: kennyd@stlouisparking.com
St. Louis Parking Co
1617 S 3rd St, St. Louis, MO 63104
Phone: (314) 241-7777 Ext: 103
Fax: (877) 310-9169
Email: kennyd@stlouisparking.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.8 - Door closing force | 1001.2(a)(8) | Yes | No | Provide and record the door closing force. | 9/4/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work with 24/7 support. | 9/4/2019 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 1001.2(c)(2) | No | No | The car top light shall work. | 10/6/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 4/21/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 4/20/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit light shall be operational. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 10/6/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational on battery back up and normal operation. | 8/26/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/6/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 10/6/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | All machine rooms or enclosures shall have a self-locking door and shall be operable from the interior space without the use of a key. | 10/6/2025 |
| A17.1-1996 : Elevators | 3.20 - Governor rope | 206.5e Governor Rope Tag | No | No | 2.18.5.3 - Replace the missing governor rope tag. | 10/6/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Only tests completed this day: Ran the hoistway, tested seismic device, pull out/pull thru, governor switch/jaw, checked pit switches. The following items must still be completed to finish the annual and category 5 test: 1. Unintended motion car down with 125% rated load. 2. Unintended motion car up with empty car. 3. Brake will stop and hold 125% of rated load. 4. Brake will hold 125% of rated lad with main power removed. 5. Compress car buffer with rated load at rated speed. 6. Compress counterweight buffer with empty car at rated speed. 7. Set the safeties with car at rated load and rated speed. 8. Fire service. 9. Test car phone, emergency light and bell with 110v power removed. 10. Door closing force. | 8/31/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Must still complete the following for the category 5 test and annual inspection: Set the safeties with car at rated load and rated speed, Fire Service, test car phone, emergency light and bell with 110v power removed, door closing force. | 4/5/2023 |
| A17.1-1996 : Elevators | 5.6 - Governor-rope tension devices | 206.7 | Yes | No | Governor tail tension sheave is siting on the pit floor. Governor rope needs to be shortened. | 6/21/2023 |
| A17.1-1996 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10.1.2 - Protection not functioning | Yes | No | Seismic/ Ring and string does not work. | 12/20/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/6/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | MCP Fire service testing must be properly documented monthly on log sheet. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | Disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | All machine rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | No | No | Clean cartop. | 10/6/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/6/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service log in the machine room has to be filled out every month after testing. | 10/6/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Hall doors at first floor need to be realigned to correct gap at the bottom. | 11/11/2025 |
| A17.1-1996 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10.1.2 - Protection not functioning | Yes | No | Seismic operation is not working. | 11/11/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Car is out of service and reinspection could not be completed. | 4/24/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Hall doors at first floor need to be realigned to correct gap at the bottom. | 4/24/2026 |
| A17.1-1996 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10.1.2 - Protection not functioning | Yes | No | Seismic operation is not working. | 4/24/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | Yes | Red Tagged for under sized governor rope, bad tail sheave and governor just barely meets Otis specs for sheave depth. | 7/24/2026 |