Inspection
Inspection Details
Equipment ID
1225
1225
Inspection Date
4/10/2024
4/10/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
300
300
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
19F/21R
19F/21R
External ID
52a31f2a-514f-4cde-a0d9-1346680e01bf
52a31f2a-514f-4cde-a0d9-1346680e01bf
Location
St. Charles High School
725 N Kingshighway St, St. Charles, MO
Phone: (636) 946-1229
725 N Kingshighway St, St. Charles, MO
Phone: (636) 946-1229
Owner
Attn: St. Charles R-6 School Dist
St. Charles R-6 School Dist
3800 W Clay, St. Charles, MO 63301
Phone: (636) 443-4880
Email: tringling@stcharlessd.org
St. Charles R-6 School Dist
3800 W Clay, St. Charles, MO 63301
Phone: (636) 443-4880
Email: tringling@stcharlessd.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Only elevator equipment is allowed in machine room. | 5/23/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 8/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 8.6.1.7.5 - The emergency lowering device (ERU) shall be operational. | 8/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency light shall be operational. | 1/4/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/19/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 8/19/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Phase II key switch in car is not operating properly. Take corrective action as needed and retest. | 6/28/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/22/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 7/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Per MO State Memorandum 006, oil line from jack head going into tank in machine room is no longer allowed. Oil must go into a container in the pit, no larger than 5 gallons and not permitted to overflow. | 7/22/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it | 7/22/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove all non-elevator materials in the machine room. | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Battery lowering unit is not working. | 4/29/2026 |