Inspection
Inspection Details
Equipment ID
18363
18363
Inspection Date
4/19/2024
4/19/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Relief Valve Pressure
620
620
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
25/22
25/22
External ID
3bfae7fb-0cd4-46c9-a545-9154a15a87f5
3bfae7fb-0cd4-46c9-a545-9154a15a87f5
Location
Salvation Army- St. Louis
10740 Page Ave, St. Louis, MO
Phone: (314) 423-7770
10740 Page Ave, St. Louis, MO
Phone: (314) 423-7770
Owner
Attn: Tracy Douglas
Salvation Army- St. Louis
2900 Washington Ave, St. Louis, MO 63103
Phone: (314) 423-7770 Ext: 7722
Email: tracy.douglas@usc.salvationarmy.org
Salvation Army- St. Louis
2900 Washington Ave, St. Louis, MO 63103
Phone: (314) 423-7770 Ext: 7722
Email: tracy.douglas@usc.salvationarmy.org
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | A key switch on the car operating panel in the car is pushed in resulting in a possible electrical hazard and shall be repaired. | |||
A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | x | This elevator has an overspeed valve device installed that is not sealed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection is required. | 7/6/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | There is a oil recovery unit installed in the pit of this elevator designed to return the oil leakage from the packing gland on the cylinder head. The State of Missouri has determined that this device does not suffice for oil leakage and is only allowed for temporary use until the packing gland can be repaired/replaced. Remove the recovery unit after the packing gland has been repaired/replaced and record the oil loss per A17.1 2016 - 8.6.5.5.7 | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Seal hole in the car operating panel, potential life/limb hazard. | |||
A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | x | OSV in the pit is unsealed, provide testing. | 4/19/2024 | |
A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | Remove scavenger unit from the pit. | |||
A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | Provide code compliant means of oil recovery in the pit (buckets) | |||
A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | Remove scavenger oil lines going back to the tank. | |||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | Clean the pit. | |||
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Provide existing battery backup lowering unit to work correctly. | 4/19/2024 | |
A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | Replace missing car handrails. | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Post Phase I instructions near f/f switch in the lobby. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Provide Phase I halo ring to be readable, worn. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Hole in COP, missing switch. Seal. Potential life/limb hazard. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | x | Remove scavenger unit from the pit. | 6/5/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | x | Remove scavenger return line. | 6/5/2024 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | x | Post current State Elevator Certificate. | 6/5/2024 | |
A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | x | OSV in the pit is unsealed. Provide testing. | 6/5/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | x | Provide code compliant means to collect jack oil for each piston. | 6/5/2024 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | x | Clean the pit | 6/5/2024 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | x | Provide existing battery backup lowering unit to work. | 6/5/2024 | |
A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | x | Replace missing car hand rails. | 6/5/2024 | |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | x | Post Phase I instructions. | 6/5/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Key switch halo ring is worn and unreadable. | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | Door open function failed on Phase II. | 6/5/2024 | |
A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | Provide machine room door to be self locking (no button) | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | 3rd floor electronic directional arrow missing cover, provide. |