Inspection
Inspection Details
Equipment ID
9069
9069
Inspection Date
10/10/2018
10/10/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Relief Valve Pressure
610
610
Slide
Governor Rope Pull
n/a
n/a
Door Closing Force
27/26
27/26
External ID
5774a816-2138-4f9e-a664-71086886edaf
5774a816-2138-4f9e-a664-71086886edaf
Location
Missouri Botanical Garden-Monsanto Research Center
4500 SHAW AVE, SAINT LOUIS, MO
4500 SHAW AVE, SAINT LOUIS, MO
Owner
Missouri Botanical Garden
4344 SHAW BLVD, SAINT LOUIS, MO 63110-2226
4344 SHAW BLVD, SAINT LOUIS, MO 63110-2226
Billing
Attn: Missouri Botanical Garden
4344 SHAW BLVD, SAINT LOUIS, MO 63110-2226
4344 SHAW BLVD, SAINT LOUIS, MO 63110-2226
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Re-inspection is required. | 12/21/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The hydraulic oil cooler that is installed in the machine room has been switched off. This device cools the temperature of the oil when the elevator is being used excesively. It may be noted, that the elevator would not perform multiple runs at 100% capacity for the requried five year full load test. The building occupancy at this time is not at or near capacity at this time, which would require the elevator to perform at 100% capacity. Recmomment continual monitoring of the oil temperature and reactivate the oil cooler. | 1/15/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The hydraulic oil cooler that is installed in the machine room has been switched off. This device cools the temperature of the oil when the elevator is being used excessively. It may be noted, that the elevator would not perform multiple runs at 100 % capacity for the required five year full load test. The building occupancy at this time is not at or near capacity at this time, which would require the elevator to perform at 100% capacity. Recommend continual monitoring of the oil temperature and reactivate the oil cooler. | 1/15/2019 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | The hydraulic oil cooler that is installed in the machine room has been switched off. This device cools the temperature of the oil when the elevator is being used excessively. It may be noted, that the elevator would not perform multiple runs at 100 % capacity for the required five year full load test. The building occupancy at this time is not at or near capacity at this time, which would require the elevator to perform at 100% capacity. Recommend continual monitoring of the oil temperature and the oil cooler shall be reactivated. | 2/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. | 1/7/2021 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | The hydraulic oil cooler that is installed in the machine room has been switched off. This device cools the temperature of the oil when the elevator is being used excessively. It may be noted, that the elevator would not perform multiple runs at 100 % capacity for the required five year full load test. The building occupancy at this time is not at or near capacity at this time, which would require the elevator to perform at 100% capacity. Recommend continual monitoring of the oil temperature and the oil cooler shall be reactivated. | 1/7/2021 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: Upon activation of fireman’s emergency service phase I, the elevator car returned to the primary floor as required BUT DID NOT open the rear opening where the fireman’s phase I key is located. This shall be corrected to open the rear door where the key switch is to comply with installation code. Reinspection required in 30 days. | 1/7/2021 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | The hydraulic oil cooler that is installed in the machine room has been switched off. This device cools the temperature of the oil when the elevator is being used excessively. It may be noted, that the elevator would not perform multiple runs at 100 % capacity for the required five year full load test. The building occupancy at this time is not at or near capacity at this time, which would require the elevator to perform at 100% capacity. Recommend continual monitoring of the oil temperature and the oil cooler shall be reactivated. | 11/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 2/3/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. | 2/15/2023 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)11 | No | No | The dead end hitch for the hoisting rope has one securing clip missing in the pit. Attach clip to retain the rope properly in the wedge shackle. | 2/15/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | Emergency battery lowering device does not work. Re-inspection required | 4/2/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | Emergency battery lowering device does not work. Re-inspection required |