Inspection
Inspection Details
Equipment ID
19295
19295
Inspection Date
4/9/2024
4/9/2024
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
120/340
120/340
Door Closing Force
NA
NA
External ID
6f7de573-c844-4237-a65c-e924df27e60f
6f7de573-c844-4237-a65c-e924df27e60f
Location
MO Baptist Med Ctr
3015 N Ballas Rd, St. Louis, MO
Phone: (314) 996-5166
Email: brian.irvine@bjc.org
3015 N Ballas Rd, St. Louis, MO
Phone: (314) 996-5166
Email: brian.irvine@bjc.org
Owner
Attn: MO Baptist Medical Center
MO Baptist Medical Center
3015 N Ballas Rd, St. Louis, MO 63131
Phone: (314) 996-5412
Email: Laura.Bradbury@bjc.org
MO Baptist Medical Center
3015 N Ballas Rd, St. Louis, MO 63131
Phone: (314) 996-5412
Email: Laura.Bradbury@bjc.org
Billing
Attn: Brian Irvine
MO Baptist Medical Center
3015 N Ballas Rd, St. Louis, MO 63131
Phone: (314) 996-5412
Email: brian.irvine@bjc.org
MO Baptist Medical Center
3015 N Ballas Rd, St. Louis, MO 63131
Phone: (314) 996-5412
Email: brian.irvine@bjc.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 3/16/2022 |
| A17.1-1996 : Elevators | 2.13 - Governor,overspeed switch and seal | 1001.2(b)(28) | Yes | No | Per manufacturer's specifications, the governor sheave shall be replaced within 6 months. | 12/4/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In cab emergency telephone shall work. | 12/4/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | Phase 1 & 2 fire service shall be tested. | 12/4/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate. | 3/16/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/19/2021 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | No | No | Replace the missing hand rail in the car enclosure. | 3/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Fire service shall be tested to complete the annual inspection. | 12/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Water and oil shall not be allowed to accumulate on the pit floor. | 10/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Fire Service operation shall be tested as required. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 2.14.7 | No | No | The hoisway overhead lighting shall be operational. | 10/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Fire service operation shall be tested. | 10/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power operation shall be tested. | 10/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/21/2025 |