Inspection
Inspection Details
Equipment ID
19297
19297
Inspection Date
4/8/2024
4/8/2024
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
TBD
TBD
Governor Rope Pull
TBD
TBD
Door Closing Force
NA
NA
External ID
87c4c436-d630-4b2e-afdd-34b4bf5dd4a7
87c4c436-d630-4b2e-afdd-34b4bf5dd4a7
Location
MO Baptist Med Ctr
3015 N Ballas Rd, St. Louis, MO
Phone: (314) 996-5166
Email: brian.irvine@bjc.org
3015 N Ballas Rd, St. Louis, MO
Phone: (314) 996-5166
Email: brian.irvine@bjc.org
Owner
Attn: MO Baptist Medical Center
MO Baptist Medical Center
3015 N Ballas Rd, St. Louis, MO 63131
Phone: (314) 996-5412
Email: Laura.Bradbury@bjc.org
MO Baptist Medical Center
3015 N Ballas Rd, St. Louis, MO 63131
Phone: (314) 996-5412
Email: Laura.Bradbury@bjc.org
Billing
Attn: Brian Irvine
MO Baptist Medical Center
3015 N Ballas Rd, St. Louis, MO 63131
Phone: (314) 996-5412
Email: brian.irvine@bjc.org
MO Baptist Medical Center
3015 N Ballas Rd, St. Louis, MO 63131
Phone: (314) 996-5412
Email: brian.irvine@bjc.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | Phase 1 & 2 fire service shall be tested. | 12/4/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 3/16/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate. | 3/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 3/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The medical waste in the pit shall be removed. | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car alarm bell shall be operational on main and auxiliary power. | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lights shall be operational. | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Fire Service operation shall be tested as required. | 4/26/2024 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.19.3 | Yes | No | The governor sheave is worn and shall be replaced per Otis document "UNIQUE OR PRODUCT SPECIFIC INSPECTION PROCESS FOR TAA206028_ AND TAG2O6O2B_APOLLO GOVERNOR". Note: The sheave is in condition "C", and shall be replaced within 6 months per Otis Elevator. | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.3 | Yes | No | There is a temporary jumper installed on the controller (it was installed in 2006 according to the tag), its function shall be investigated and the appropriate action shall be taken (remove it, or make permanent if necessary) | 4/26/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Repair/alteration inspection failed. Gov on #24 was replaced by mistake by elevator contractor. Red tag issued. Governor shall be removed from service and replaced per OEM due to excessive sheave wear after 6 months, which expired 3/6/24. | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car alarm bell shall be operational on main and auxiliary power. This violation was originally cited on 9/26/23 and still not corrected. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lights shall be operational. This violation was originally cited on 9/26/23 and still not corrected. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. This violation was originally cited on 9/26/23 and still not corrected. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Fire Service operation shall be tested as required. This violation was originally cited on 9/26/23 and still not corrected. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.3 | Yes | No | There is a temporary jumper installed on the controller (it was installed in 2006 according to the tag), its function shall be investigated and the appropriate action shall be taken (remove it, or make permanent if necessary) This violation was originally cited on 9/26/23 and still not corrected. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Fire service operation shall be tested. | 10/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power operation shall be tested. | 10/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 10/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/21/2025 |