Inspection
Inspection Details
Equipment ID
26530
26530
Inspection Date
4/18/2024
4/18/2024
Inspection Type
New Installation
New Installation
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Douglas Colombatto
Douglas Colombatto
Relief Valve Pressure
445
445
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
27
27
External ID
cc050804-32b9-4115-8885-368e357ded01
cc050804-32b9-4115-8885-368e357ded01
Location
2311 Texas Ave
2311-2337 Texas Ave, St. Louis, MO
Phone: (636) 675-1877
Email: admin@cortonaproperties.com
2311-2337 Texas Ave, St. Louis, MO
Phone: (636) 675-1877
Email: admin@cortonaproperties.com
Owner
Attn: Julian Cortona
Cortona Properties, LLC
4333 Manchester Ave, St. Louis, MO 63110
Phone: (636) 675-1877
Email: admin@cortonaproperties.com
Cortona Properties, LLC
4333 Manchester Ave, St. Louis, MO 63110
Phone: (636) 675-1877
Email: admin@cortonaproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | Yes | Yes | 2.27.3.2.1 - Smoke initiation devices shall not be installed in elevator pits to initiate elevator recall unless they're listed for the environment. The heat detector in the pit does not meet these requirements. The device shall be rated for wet areas. | 5/29/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | In elevators provided with firefighters' emergency operation, a drain or sump pump shall be provided. The sump pump/drain shall have the capacity to remove a minimum of 3,000 gal/hour per elevator. The current sump pump does not meet these requirements. There is a long run (at least 30'-40') of 1 1/2" schedule 40 PVC pipe with at least a dozen 90 degree fittings decreasing the capacity of the pump. | 5/29/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | 2.8.3.3.2 - Where elevator equipment is located or its enclosure is configured such that application of water from sprinklers could cause unsafe elevator operation, means shall be provided to automatically disconnect the main line power supply to the affected elevator and any other power supplies used to move the elevator upon or prior to the application of water. When tested, the heat detector associated with the sprinkler in the control space did not activate the shunt trip and remove power as required. | 5/29/2024 |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.6 | Yes | No | 2.1.6.2 - Building construction making an angle less than 75 degrees with the horizontal shall not project more than 4 inches inside the hoistway enclosure unless the top surface of the projection is beveled at an angle not less than 75 degrees with the horizontal. All the ledge in the hoistway including the pit, projecting over 4" shall be beveled at no less than 75 degrees from the horizontal as required. | 5/29/2024 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | A disconnect protecting the cab lighting branch circuit shall be located in the elevator machine room or control space. The lighting disconnect in the control space currently disconnects the GFCI receptable in that space. It shall disconnect and protect the car lighting branch circuit as required. | 5/29/2024 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | The main line disconnect in the control space has internal metal parts that are not secure. This shall be corrected. | 5/29/2024 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.3 | Yes | No | 2.7.3.3.1 - A permanent, fixed, noncombustible ladder or stair shall be provided where the floor of the room or the space above or below the floor or roof from which the means of access leads, or where the distance between floor levels in the room or space, is more than 8 inches. This applies to the 14" difference in floor heights between the garage floor and the platform used for elevator control space access. | 5/29/2024 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.3 | Yes | No | 2.7.3.3.5 - A permanent, noncombustible platform or floor shall be provided at the top of the stairs conforming with the following: (a) Railings conforming to 2.10.2 shall be provided on each open side. (b) The floor of the platform shall be at the level of not more than 8 inches below the level of the access-door sill. (c) The depth of the platform shall be not less than 29.5 inches and the width not less than the width of the door. (d) The size of the platform shall be sufficient to permit the full swing of the door plus 24 inches from the top riser to the swing line of the door. The concrete floor or platform providing access to the control space shall be in compliance with (a) and (d) above, and also shall be equipped with standard railing meeting the requirements of A17.1 2016 2.10.2. | 5/29/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Fire service testing must be documented monthly. | 6/16/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. The extinguisher is expired. | 6/16/2025 |