Inspection
Inspection Details
Equipment ID
20640
20640
Inspection Date
4/18/2024
4/18/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
500
500
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21
21
External ID
6a09b10e-c50b-47b7-af1b-86fc40775335
6a09b10e-c50b-47b7-af1b-86fc40775335
Location
Mercy Rehabilitation Hospital
14561 N Outer 40 Rd, Chesterfield, MO
Phone: (314) 881-4020
14561 N Outer 40 Rd, Chesterfield, MO
Phone: (314) 881-4020
Owner
Attn: Mercy Rehabilitation Hospital
Mercy Rehabilitation Hospital
14561 N Outer 40 Rd, Chesterfield, MO 63017
Phone: (000) 000-0000
Email: dmmullen@mrhsl.com
Mercy Rehabilitation Hospital
14561 N Outer 40 Rd, Chesterfield, MO 63017
Phone: (000) 000-0000
Email: dmmullen@mrhsl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 1/9/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 10/25/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | The category 5 test shall be conducted and witnessed on the overspeed valve in 2022. | 5/1/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the elevator machine room. | 1/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Capacity tag in car shall be replaced, marking have been erased. | 1/9/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | A category 5 test shall be performed on the overspeed valve within 90 days. Not currently sealed or tagged. Multi-year violation. | 10/25/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/9/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 1/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Capacity tag in car shall be replaced. Markings have been erased. Multi-year violation now requiring re-inspection. | 10/25/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. Remove excess debris. | 1/9/2024 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency lighting shall work. | 10/31/2024 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor shall work at all floors. | 10/31/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Replace piston packing glands. Excessively either recovering pit bucket oil or adding oil, per loss log. | 4/17/2026 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | No | No | Clean cartop. | 4/17/2026 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Tighten/repair car interior handrail. It is missing the stand-off mount. | 4/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | OSV shall have current testing tag. Tested in 2023, not tagged. | 4/17/2026 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Replace/reinstall missing handrail and repair car wall panel that is detached. | 4/17/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. No documentation of any kind for 6/2024 to present. | 4/17/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing must be documented monthly. | 4/17/2026 |