Inspection
Inspection Details
Equipment ID
907
907
Inspection Date
2/29/2024
2/29/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Joseph Ammons
Joseph Ammons
Relief Valve Pressure
0
0
Slide
0
0
Governor Rope Pull
0
0
Door Closing Force
26
26
External ID
3d145a10-c518-480b-a01f-3036538694c7
3d145a10-c518-480b-a01f-3036538694c7
Location
Broadway Bldg
221 W High St, Jefferson City, MO
Phone: (573) 522-5614
Email: haley.barron@oa.mo.gov
221 W High St, Jefferson City, MO
Phone: (573) 522-5614
Email: haley.barron@oa.mo.gov
Owner
Attn: Brian Jaco
State of MO- Broadway Bldg-INTERAGENCY
221 W High St, Jefferson City, MO 65101
Phone: (573) 751-6329
Email: brian.jaco@oa.mo.gov
State of MO- Broadway Bldg-INTERAGENCY
221 W High St, Jefferson City, MO 65101
Phone: (573) 751-6329
Email: brian.jaco@oa.mo.gov
Billing
Attn: INTERAGECNY
OA-FMDC- HST RM 730-INTERAGECNY
PO Box 809, Jefferson City, MO 65102
Phone: (000) 000-0000
OA-FMDC- HST RM 730-INTERAGECNY
PO Box 809, Jefferson City, MO 65102
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Main hoist ropes rouged and undersized. | 1/27/2020 | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Main hoisting ropes rouged, and undersized. | 2/1/2021 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Emergency phone working, but not identifying location. | 2/1/2022 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 2/29/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | x | 6th floor landing door has worn gib. | 2/1/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Provide FFS testing log in machine room. | 2/29/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | x | Emergency power not tested at time of inspection. | 2/1/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | Provide type ABC fire extinguisher in machine room. | 2/29/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide MCP in machine room. | 2/29/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 2/29/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working. | 2/9/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | x | Standby power not tested at time of inspection. | 2/9/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Provide an up to date fire extinguisher in machine room. | 2/29/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide an MCP in machiner room. | 2/29/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 2/29/2024 | ||
| MO Minimum : Elevators | (J) - Counterweights | (J)2 | Counterweight rollers worn, replace. | 5/20/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Floor 4 landing door missing one gib. | 7/15/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Car selector on cartop needs new guides. | 5/20/2024 |