Inspection
Inspection Details
Equipment ID
220
220
Inspection Date
11/14/2018
11/14/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Gerald Jordan
Gerald Jordan
Relief Valve Pressure
Slide
Governor Rope Pull
n/a
n/a
Door Closing Force
FR 25 R 25
FR 25 R 25
External ID
89f9de1c-7501-41cf-b43b-f82ac00d55d1
89f9de1c-7501-41cf-b43b-f82ac00d55d1
Location
South Tower
770 SOUTH AVE, SPRINGFIELD, MO
770 SOUTH AVE, SPRINGFIELD, MO
Owner
Springfield Housing Authority
421 W MADISON ST, SPRINGFIELD, MO 65806-3060
421 W MADISON ST, SPRINGFIELD, MO 65806-3060
Billing
Attn: Springfield Housing Authority
421 W MADISON ST, SPRINGFIELD, MO 65806-3060
421 W MADISON ST, SPRINGFIELD, MO 65806-3060
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | 1/5/21: Car Door restrictor shall work {front and rear}. (REINSPECTION REQUIRED) | 8/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | 1/5/21: Car Door restrictor shall work {front and rear}. (REINSPECTION REQUIRED) | 8/11/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly. | 5/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car Door restrictor shall work. Front and Rear. | 3/30/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | H(8) Replace missing electrical box cover. | 5/3/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | H(5) Machine room lighting needs to be repaired | 5/3/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. MUST RETURN TO COMPLETE. Required within 30days | 3/30/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car Door restrictor shall work. Front and Rear. | 3/30/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. MUST RETURN TO COMPLETE. Required within 30days | 3/30/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall give proper location message, no Location message given. (REINSPECTION > 14days) | 11/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Key Switch bezel missing in COP | 11/29/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Remove/attach styrofoam insulation board at top rear of Hoistway(covering exterior ventilation vent). Currently just wedged behind piping, about to fall. | 11/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | G(1)/A17.1-2016:8.6.1.2.1(a)/2.40 Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. | 11/29/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Car hoist ropes undersized, replace per code | 8/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide onsite MCP | 6/3/2024 |