Inspection
Inspection Details
Equipment ID
13861
13861
Inspection Date
12/29/2017
12/29/2017
Inspection Type
Alteration
Alteration
Inspector Name
Dennis Nelson
Dennis Nelson
Mechanic Name
James Dalton
James Dalton
Relief Valve Pressure
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
5ad0a2c1-4855-4295-b20b-b23615e18e11
5ad0a2c1-4855-4295-b20b-b23615e18e11
Location
Hollywood Casino St. Louis
777 CASINO CENTER DR, MARYLAND HEIGHTS, MO
777 CASINO CENTER DR, MARYLAND HEIGHTS, MO
Owner
Hollywood Casino St. Louis
777 CASINO DR, MARYLAND HEIGHTS, MO 63043
777 CASINO DR, MARYLAND HEIGHTS, MO 63043
Billing
Attn: Hollywood Casino St. Louis
777 CASINO CENTER DR, MARYLAND HEIGHTS, MO 63043-4821
777 CASINO CENTER DR, MARYLAND HEIGHTS, MO 63043-4821
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 10/10/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 10/10/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test counterweight buffer at rated speed. Re-inspection required | 10/19/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | No | No | Need to replace missing capacity plate in car | 9/15/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has standing water, need to remove water and repair sump pump | 10/15/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Replace missing phase I and II fire service operating instructions signs. | 7/23/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | When the elevator is on phase II fire service at the alternate landing, it will not revert back to phase I fire recall when the in car phase II fire service switch is turned to off. Needs repaired, Re-inspection required | 7/23/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Elevator car door restrictor does not work, needs repaired. Re-inspection required | 7/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Need to replace missing door gibb on 2nd floor Halldoor | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Need signs "In case of Fire, use Stairs" | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Doors do not stay open on Phase I fire service. Re-inspection required | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | When the elevator is on phase II fire service at the alternate landing, it will not revert back to phase I fire recall when the in car phase II fire service switch is turned to off. Needs repaired, Re-inspection required |