Inspection
Inspection Details
Equipment ID
18471
18471
Inspection Date
5/3/2024
5/3/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
550
550
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26
26
External ID
ca2bfa11-b446-436b-8a7f-84848df8ee6b
ca2bfa11-b446-436b-8a7f-84848df8ee6b
Location
City Place 5
845 N New Ballas Ct, Creve Coeur, MO
Phone: (314) 993-5800
845 N New Ballas Ct, Creve Coeur, MO
Phone: (314) 993-5800
Owner
Attn: Jessica Shaw Assistant Property Manager
SNH Medical Office Properties Trust c/o RMR Real Estate Service
1660 Lincoln St, Ste 1910, Denver, CO 80264
Phone: (314) 392-0400
Email: Jessica.shaw@cushwake.com
SNH Medical Office Properties Trust c/o RMR Real Estate Service
1660 Lincoln St, Ste 1910, Denver, CO 80264
Phone: (314) 392-0400
Email: Jessica.shaw@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 6/1/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/1/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/26/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/24/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | Yes | No | Fire service phase II switch key shall not be removable in "ON" position. | 5/1/2026 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | Yes | No | Machine room oil coolers are wired to cab lighting circuit. Shall be dedicated circuits. | 5/1/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/1/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. Missing PM/repair/callback/testing logs for 2023, 2024 and 2025. | 5/1/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track (1st Floor). | 5/1/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | No | No | Replace unreadable in-car capacity plate/unit number plate. | 5/1/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Fire service testing must be documented monthly. | 5/1/2026 |