Inspection
Inspection Details
Equipment ID
13329
13329
Inspection Date
5/13/2024
5/13/2024
Inspection Type
Reinspection
Reinspection
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
Brent Davis
Brent Davis
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
04c03892-ce31-454b-af50-dc9d06c2f9e2
04c03892-ce31-454b-af50-dc9d06c2f9e2
Location
Lammert Building
911 Washington Ave, St. Louis, MO
Phone: (314) 241-7500
911 Washington Ave, St. Louis, MO
Phone: (314) 241-7500
Owner
Attn: Technology Entrepreneur Center T-Rex
Technology Entrepreneur Center T-Rex
911 Washington Ave, St. Louis, MO 63101
Phone: (314) 241-7500
Email: gwyn@downtowntrex.org
Technology Entrepreneur Center T-Rex
911 Washington Ave, St. Louis, MO 63101
Phone: (314) 241-7500
Email: gwyn@downtowntrex.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (E) - Machines | (E)1 | No | No | Traction machine is making a loud noise and vibrating. Repair | 3/25/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Turn down fire tabs on all hoistway doors. | 3/25/2026 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | Test brake with 125% rated load. Did not red tag. | 10/21/2019 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Test car and counterweight buggers at rated speed. Did not red tag. | 10/21/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need maintenance control program on site | 3/25/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/25/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Ropes failed gauge test needs replacing | 3/25/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/25/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 3/25/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace hoist ropes, red rouge reduced diameter within 30 days | 5/13/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Make pit light operable | 3/25/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | Make pit stop switch operable. | 3/25/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from pit | 3/25/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | Adjust car door operator. Excessive force | 3/25/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Complete 5 year test. | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Pit stop switch is functional but toggle switch is broken off. Toggle needs replaced. |