Inspection
Inspection Details
Equipment ID
8859
8859
Inspection Date
5/13/2024
5/13/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
470
470
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
18
18
External ID
448f662a-3d46-445d-83d1-2b1be3d7d6a7
448f662a-3d46-445d-83d1-2b1be3d7d6a7
Location
110 N Newstead Condo
110 N Newstead Ave, St. Louis, MO
Phone: (314) 781-0303
110 N Newstead Ave, St. Louis, MO
Phone: (314) 781-0303
Owner
Attn: Bob Petersen
110 N Condominium LLP c/o Civitas Real Estate Services, LLC
7292 Manchester Rd, St. Louis, MO 63143
Phone: (314) 802-4344
Email: rpetersen@civitasrealestateservices.com
110 N Condominium LLP c/o Civitas Real Estate Services, LLC
7292 Manchester Rd, St. Louis, MO 63143
Phone: (314) 802-4344
Email: rpetersen@civitasrealestateservices.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone needs to work. | 6/24/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative emergency phone. No active phone line. | 5/13/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Perform OSV test on or before next annual inspection date. | 5/13/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP. | 4/28/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil from the sump hole. | 4/28/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Determine if sump pump works, if not replace. | 4/28/2026 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | Unsealed. | 5/13/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Provide guard on bulbs, to prevent accidental contact or breakage. Or change egg crate style ceiling in car. | 4/28/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work on normal or emergency 110v power | 5/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Machine room ventilation fan has been removed, replace as needed. | 4/28/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | 4/28/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Car top inspection function not working, make so. | 7/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, have serviced or replaced | 4/28/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 4/28/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Machine room ventilation has been removed, need to replace | 4/28/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Car top inspection controls are not working | 4/28/2026 |