Inspection
Inspection Details
Equipment ID
18753
18753
Inspection Date
10/8/2018
10/8/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
a2f30eae-51c6-4623-8de3-6dd982f87d99
a2f30eae-51c6-4623-8de3-6dd982f87d99
Location
Station Plaza- Bldg D
140 S KIRKWOOD RD, KIRKWOOD, MO
140 S KIRKWOOD RD, KIRKWOOD, MO
Owner
Maxus Properties
141 E MADISON AVE, SAINT LOUIS, MO 63122-4330
141 E MADISON AVE, SAINT LOUIS, MO 63122-4330
Billing
Attn: Kirkwood Station Plaza
141 E MADISON AVE, KIRKWOOD, MO 63122-4330
141 E MADISON AVE, KIRKWOOD, MO 63122-4330
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In cab emergency phone shall work. | 1/25/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/14/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Car missing cover for lights | 11/14/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Replace the missing tile on the car floor. It is creating a tripping hazard. | 11/14/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no operating certificate displayed in machine room. A current MO State operating certificate shall be displayed in the elevator machine room. | 11/14/2025 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | The car door restrictor is not operating properly. Take corrective action. | 6/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Unable to run car onto stopring to complete pressure test. Need relief pressure and 15 min stand test to complete. | 12/2/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. | 12/2/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision place over it. | 12/2/2025 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | No | No | Car top light shall be operational. | 12/2/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision place over it. | 5/12/2026 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | No | No | Car top light shall be operational. | 5/12/2026 |