Inspection
Inspection Details
Equipment ID
17061
17061
Inspection Date
5/9/2024
5/9/2024
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Benjamin Williams
Benjamin Williams
Relief Valve Pressure
640
640
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
21/20
21/20
External ID
142569a1-0cec-48c9-a5ec-8291eeaebba0
142569a1-0cec-48c9-a5ec-8291eeaebba0
Location
Target- St. Louis
4255 Hampton Ave, St. Louis, MO
Phone: (314) 802-0122
4255 Hampton Ave, St. Louis, MO
Phone: (314) 802-0122
Owner
Attn: Timothy Fournier
Target Vertical Transportation
PO Box 1356, Minneapolis, MN 55402
Phone: (612) 304-5759
Email: TargetVT@target.com
Target Vertical Transportation
PO Box 1356, Minneapolis, MN 55402
Phone: (612) 304-5759
Email: TargetVT@target.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post Mo State operating permit in machine room | 10/19/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Need testing procedures in MCP on or before 1/1/22 | 5/22/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room Overspeed valve set at 171 | 2/10/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Front and rear restrictors shall work. | 7/3/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Machine room fire extinguisher shall be permanently mounted to the wall. | 7/3/2025 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | Lighting disconnect fused improperly. Replace 20A fuse with proper 15A. | 7/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | Hall calls shall work. | 7/3/2025 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Adjust upthrusts for proper clearances (2nd floor front). | 7/3/2025 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Adjust upthrusts for proper lower gap opening. | 7/3/2025 |
| A17.1-2016 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | Yes | No | Adjust hoistway access limit (PIT) for proper stopping heights. | 7/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | INCOMPLETE: Remaining testing needed is as follows: pump pressures and speed, relief pressure, OSV, rear door torque, phase I & II fire service, FAID and recalls, battery lowering, COP stop, low oil, and 15 min static testing. | 7/3/2025 |